Mains Supply; Protection And Features; Ambient Conditions - Danfoss VLT DriveMotor FCP 106 Operating Instructions Manual

Hide thumbs Also See for VLT DriveMotor FCP 106:
Table of Contents

Advertisement

Specifications

7.3 Mains Supply

Mains supply (L1, L2, L3)
Supply voltage
Mains voltage low/mains drop-out:
During low mains voltage or a mains drop-out, the frequency converter continues until the intermediate circuit
voltage drops below the minimum stop level, which corresponds typically to 15% below the lowest rated supply
voltage of the frequency converter. Power-up and full torque cannot be expected at mains voltage lower than 10%
below the lowest rated supply voltage of the frequency converter.
Supply frequency
Max. imbalance temporary between mains phases
True Power Factor (λ)
Displacement Power Factor (cosφ)
Switching on the input supply L1, L2, L3 (power-ups)
Environment according to EN 60664-1
The unit is suitable for use on a circuit capable of delivering not more than
100,000 RMS symmetrical Amperes, 480 V maximum, with fuses used as branch circuit protection
10,000 RMS symmetrical Amperes, 480 V maximum, with circuit breakers used as branch circuit protection

7.4 Protection and Features

Protection and features
Electronic thermal motor protection against overload.
Temperature monitoring of the heat sink ensures that the frequency converter trips when the temperature reaches
90 °C ±5°C. An overload temperature cannot be reset until the temperature of the heatsink is below 70 °C ±5 °C
(Guideline - these temperatures may vary for different power sizes, enclosures etc.). The frequency converter auto
derating function ensures that the heatsink temperature does not reach 90 °C.
The frequency converter is protected against short-circuits between motor terminals U, V, W.
When a motor phase is missing, the frequency converter trips and issues an alarm.
When a mains phase is missing, the frequency converter trips or issues a warning (depending on the load).
Monitoring of the intermediate circuit voltage ensures that the frequency converter trips, when the intermediate
circuit voltage is too low or too high.
The frequency converter is protected against earth faults on motor terminals U, V, W.
All control terminals and relay terminals 01-03/04-06 comply with PELV (Protective Extra Low Voltage). However
this does not apply to grounded Delta leg above 400 V.

7.5 Ambient Conditions

Environment
Enclosure
Stationary vibration (IEC 60721-3-3 Class 3M6)
Non-stationary vibration (IEC 60721-3-3 Class 3M6)
Relative humidity (IEC 60721-3-3; Class 3K4 (non-condensing))
Aggressive environment (IEC 60721-3-3)
Test method according to IEC 60068-2-43
Ambient temperature
Minimum ambient temperature during full-scale operation
Minimum ambient temperature at reduced performance
Temperature during storage
Temperature during transport
MG03L202
Operating Instructions
Danfoss A/S © Rev. 06/2014 All rights reserved.
380-480 V ±10%
3.0% of rated supply voltage
≥ 0.9 nominal at rated load
near unity (>0.98)
Max. 2 times/min.
overvoltage category III/pollution degree 2
5%-95% during operation
40 °C (24-hour average)
50/60 Hz
7
7
IP54/Type 3R
2.0 g
25.0 g
Class 3C3
H2S (10 days)
-10 °C
-20 °C
-25 to +65 °C
-25 to +70 °C
39