Commissioning
If warnings or alarms occur, see chapter 6.5 Warning and
Alarm Types or chapter 6.6 List of Warnings and Alarms.
5.5 Operation
5.5.1 Uploading/Downloading Data to/from
the LCP
1.
Press [Off] to stop the motor before uploading or
downloading data.
2.
Press [Main Menu], select parameter 0-50 LCP Copy
and press [OK].
5
5
3.
Select [1] All to LCP to upload data to the LCP or
select [2] All from LCP to download data from the
LCP.
4.
Press [OK]. A progress bar shows the uploading or
downloading progress.
5.
Press [Hand On] or [Auto On] to return to normal
operation.
5.5.2 Changing Parameter Settings
Access and change parameter settings from the Quick
Menu or from the Main Menu. The Quick Menu only gives
access to a limited number of parameters.
1.
Press [Quick Menu] or [Main Menu] on the LCP.
2.
Press [
groups, press [OK] to select a parameter group.
3.
Press [
press [OK] to select a parameter.
4.
Press [
setting.
5.
Press [◄] [►] to shift digit when a decimal
parameter is in the editing state.
6.
Press [OK] to accept the change.
7.
Press either [Back] twice to enter Status, or press
[Main Menu] once to enter the Main Menu.
View changes
Quick Menu Q5 - Changes Made lists all parameters
changed from default settings.
•
The list only shows parameters, which are
changed in the current edit set-up.
•
Parameters, which were reset to default values,
are not listed.
•
The message Empty indicates that no parameters
are changed.
30
VLT
▲
▼
] [
] to browse through the parameter
▲
▼
] [
] to browse through the parameters,
▲
▼
] [
] to change the value of a parameter
Danfoss A/S © 11/2016 All rights reserved.
®
Decentral Drive FCD 302
5.5.3 Restoring Default Settings
NOTICE
Risk of losing programming, motor data, localization, and
monitoring records by restoration of default settings. To
provide a back-up, upload data to the LCP before initiali-
zation.
Restoring the default parameter settings is done by initiali-
zation of the frequency converter. Initialization is carried
out through parameter 14-22 Operation Mode
(recommended) or manually.
•
Initialization using parameter 14-22 Operation
Mode does not reset the frequency converter
settings such as hours run, serial communication
selections, personal menu settings, fault log,
alarm log, and other monitoring functions.
•
Manual initialization erases all motor,
programming, localization, and monitoring data
and restores factory default settings.
Recommended initialization procedure via
parameter 14-22 Operation Mode
1.
Press [Main Menu] twice to access parameters.
2.
Scroll to parameter 14-22 Operation Mode and
press [OK].
3.
Scroll to [2] initialization and press [OK].
4.
Remove power to the unit and wait for the
display to turn off.
5.
Apply power to the unit.
Default parameter settings are restored during start-up.
The start-up may take slightly longer than normal.
6.
Alarm 80, Drive initialized to default value is shown.
7.
Press [Reset] to return to operating mode.
Manual initialization procedure
1.
Remove power to the unit and wait for the
display to turn off.
2.
Press and hold [Status], [Main Menu], and [OK] at
the same time while applying power to the unit
(approximately 5 s or until audible click and fan
starts).
Factory default parameter settings are restored during
start-up. The start-up may take slightly longer than usual.
Manual initialization does not reset the following
frequency converter information:
•
Parameter 15-00 Operating hours.
•
Parameter 15-03 Power Up's.
•
Parameter 15-04 Over Temp's.
•
Parameter 15-05 Over Volt's.
MG04F502