Operation; Uploading/Downloading Data To/From The Lcp; Changing Parameter Settings; Restoring Default Settings - Danfoss VLT Decentral Drive FCD 302 Operating Manual

Hide thumbs Also See for VLT Decentral Drive FCD 302:
Table of Contents

Advertisement

Commissioning
If warnings or alarms occur, see chapter 6.5 Warning and
Alarm Types or chapter 6.6 List of Warnings and Alarms.

5.5 Operation

5.5.1 Uploading/Downloading Data to/from
the LCP
1.
Press [Off] to stop the motor before uploading or
downloading data.
2.
Press [Main Menu], select parameter 0-50 LCP Copy
and press [OK].
5
5
3.
Select [1] All to LCP to upload data to the LCP or
select [2] All from LCP to download data from the
LCP.
4.
Press [OK]. A progress bar shows the uploading or
downloading progress.
5.
Press [Hand On] or [Auto On] to return to normal
operation.

5.5.2 Changing Parameter Settings

Access and change parameter settings from the Quick
Menu or from the Main Menu. The Quick Menu only gives
access to a limited number of parameters.
1.
Press [Quick Menu] or [Main Menu] on the LCP.
2.
Press [
groups, press [OK] to select a parameter group.
3.
Press [
press [OK] to select a parameter.
4.
Press [
setting.
5.
Press [◄] [►] to shift digit when a decimal
parameter is in the editing state.
6.
Press [OK] to accept the change.
7.
Press either [Back] twice to enter Status, or press
[Main Menu] once to enter the Main Menu.
View changes
Quick Menu Q5 - Changes Made lists all parameters
changed from default settings.
The list only shows parameters, which are
changed in the current edit set-up.
Parameters, which were reset to default values,
are not listed.
The message Empty indicates that no parameters
are changed.
30
VLT
] [
] to browse through the parameter
] [
] to browse through the parameters,
] [
] to change the value of a parameter
Danfoss A/S © 11/2016 All rights reserved.
®
Decentral Drive FCD 302

5.5.3 Restoring Default Settings

NOTICE
Risk of losing programming, motor data, localization, and
monitoring records by restoration of default settings. To
provide a back-up, upload data to the LCP before initiali-
zation.
Restoring the default parameter settings is done by initiali-
zation of the frequency converter. Initialization is carried
out through parameter 14-22 Operation Mode
(recommended) or manually.
Initialization using parameter 14-22 Operation
Mode does not reset the frequency converter
settings such as hours run, serial communication
selections, personal menu settings, fault log,
alarm log, and other monitoring functions.
Manual initialization erases all motor,
programming, localization, and monitoring data
and restores factory default settings.
Recommended initialization procedure via
parameter 14-22 Operation Mode
1.
Press [Main Menu] twice to access parameters.
2.
Scroll to parameter 14-22 Operation Mode and
press [OK].
3.
Scroll to [2] initialization and press [OK].
4.
Remove power to the unit and wait for the
display to turn off.
5.
Apply power to the unit.
Default parameter settings are restored during start-up.
The start-up may take slightly longer than normal.
6.
Alarm 80, Drive initialized to default value is shown.
7.
Press [Reset] to return to operating mode.
Manual initialization procedure
1.
Remove power to the unit and wait for the
display to turn off.
2.
Press and hold [Status], [Main Menu], and [OK] at
the same time while applying power to the unit
(approximately 5 s or until audible click and fan
starts).
Factory default parameter settings are restored during
start-up. The start-up may take slightly longer than usual.
Manual initialization does not reset the following
frequency converter information:
Parameter 15-00 Operating hours.
Parameter 15-03 Power Up's.
Parameter 15-04 Over Temp's.
Parameter 15-05 Over Volt's.
MG04F502