Parameter Settings; Uploading/Downloading Data To/From The Lcp; Changing Parameter Settings; Restoring Default Settings - Danfoss VLT AutomationDrive FC 301 Operating Instructions Manual

0.25-75 kw
Hide thumbs Also See for VLT AutomationDrive FC 301:
Table of Contents

Advertisement

Commissioning
D. Operation keys and reset
Operation keys are located at the bottom of the LCP.
Key
18
Hand On
19
Off
20
Auto On
5
5
21
Reset
Table 5.5 Legend to Illustration 5.1, Operation Keys and Reset
NOTICE
The display contrast can be adjusted by pressing [Status]
and the [
]/[

5.3.3 Parameter Settings

Establishing the correct programming for applications
often requires setting functions in several related
parameters. Details for parameters are provided in
chapter 9.2 Parameter Menu Structure.
Programming data is stored internally in the frequency
converter.
For back-up, upload data into the LCP memory.
To download data to another frequency
converter, connect the LCP to that unit and
download the stored settings.
Restoring factory default settings does not
change data stored in the LCP memory.
5.3.4 Uploading/Downloading Data to/from
the LCP
1.
Press [Off] to stop the motor before uploading or
downloading data.
2.
Press [Main Menu] 0-50 LCP Copy and press [OK].
3.
Select [1] All to LCP to upload data to the LCP or
select [2] All from LCP to download data from the
LCP.
4.
Press [OK]. A progress bar shows the uploading
or downloading progress.
5.
Press [Hand On] or [Auto On] to return to normal
operation.
24
Function
Starts the frequency converter in local
control.
An external stop signal by control input
or serial communication overrides the
local hand on.
Stops the motor but does not remove
power to the frequency converter.
Puts the system in remote operational
mode.
Responds to an external start command
by control terminals or serial communi-
cation.
Resets the frequency converter manually
after a fault has been cleared.
] keys.
Danfoss A/S © Rev. 07/2014 All rights reserved.
Operating Instructions

5.3.5 Changing Parameter Settings

Parameter settings can be accessed and changed from the
Quick Menu or from the Main Menu. The Quick Menu only
gives access to a limited number of parameters.
1.
2.
3.
4.
5.
6.
7.
View changes
Quick Menu Q5 - Changes Made lists all parameters
changed from default settings.

5.3.6 Restoring Default Settings

NOTICE
Risk of losing programming, motor data, localisation, and
monitoring records by restoration of default settings. To
provide a back-up, upload data to the LCP before initiali-
sation.
Restoring the default parameter settings is done by initiali-
sation of the frequency converter. Initialisation is carried
out through 14-22 Operation Mode (recommended) or
manually.
Press [Quick Menu] or [Main Menu] on the LCP.
Press [
] [
] to browse through the parameter
groups, press [OK] to select a parameter group.
Press [
] [
] to browse through the parameters,
press [OK] to select a parameter.
Press [
] [
] to change the value of a parameter
setting.
Press [◄] [►] to shift digit when a decimal
parameter is in the editing state.
Press [OK] to accept the change.
Press either [Back] twice to enter Status, or press
[Main Menu] once to enter the Main Menu.
The list only shows parameters, which have been
changed in the current edit set-up.
Parameters, which have been reset to default
values, are not listed.
The message Empty indicates that no parameters
have been changed.
Initialisation using 14-22 Operation Mode does not
reset frequency converter settings, such as
operating hours, serial communication selections,
personal menu settings, fault log, alarm log, and
other monitoring functions.
Manual initialisation erases all motor,
programming, localisation, and monitoring data
and restores factory default settings.
MG33AP02

Advertisement

Table of Contents
loading

This manual is also suitable for:

Vlt automationdrive fc 302

Table of Contents