Electrical Installation
Control terminals
BUS TER.
OFF
ON
61 68 69
18 19
27 29 42 45 50 53 54
0/4-20mA A OUT / DIG OUT
Illustration 4.10 Control Terminals
Terminal
Function
Configuration
number
12
+24 V output
18
Digital input *PNP/NPN
19
Digital input *PNP/NPN
20
Com
27
Digital input *PNP/NPN
29
Digital input *PNP/NPN
50
+10 V output
53
Analog input *0-10 V/0-20 mA/
4-20 mA
54
Analog input *0-10 V/0-20 mA/
4-20 mA
55
Com
42
12 bit
*0-20 mA/4-20
mA/DO
45
12 bit
*0-20 mA/4-20
mA/DO
1, 2, 3
Relay 1
1,2 NO 1,3 NC
4, 5, 6
Relay 2
4,5 NO 4,6 NC
Table 4.3 Control Terminal Functions
* indicates default setting
Note: PNP/NPN is common for terminals 18, 19 and 27
4.8.2 Load Sharing
Load sharing is not permissible.
4.8.3 Brake
The frequency converter has no internal brake. An external
brake can be connected between the UDC+ and UDC-
terminals. Limit the voltage between these terminals to
maximum 768 V.
MG03L202
Operating Instructions
0/4-20mA A OUT / DIG OUT
12 20 55
GND
GND
Factory
setting
Start
No operation
Coast inverse
Jog
Ref1
Ref2
Analog
Analog
[9] Alarm
[5] Drive
running
Danfoss A/S © Rev. 06/2014 All rights reserved.
NOTICE
Increasing voltage beyond the limit will decrease
lifetime, and may permanently damage the frequency
converter.
4
4
21