Commissioning
C. Navigation keys and indicator lights (LEDs)
6
Com LED: Flashes when bus communication is communi-
cating.
7
Green LED/On: Control section is working.
8
Yellow LED/Warn.: Indicates a warning.
9
Flashing Red LED/Alarm: Indicates an alarm.
10 [Back]: For moving to the previous step or layer in the
navigation structure
11 [
] [
] [►]: For maneuvering between parameter groups,
parameters and within parameters. Can also be used for
setting local reference.
5
5
12 [OK]: For selecting a parameter and for accepting changes to
parameter settings
D. Operation keys and indicator lights (LEDs)
13
[Hand On]: Starts the motor and enables control of the
frequency converter via the LCP.
NOTICE
Terminal 27 Digital Input (5-12 Terminal 27 Digital
Input) has coast inverse as default setting. This
means that [Hand On] does not start the motor if
there is no 24 V to terminal 27. Connect terminal
12 to terminal 27.
14
[Off/Reset]: Stops the motor (Off). If in alarm mode the
alarm is reset.
15
[Auto On]: Frequency converter is controlled either via
control terminals or serial communication.
5.2.2 Connect LCP Cable
1
Control panel
2
Panel door
Illustration 5.3 LCP Remote Mounting
To view or change the frequency converter settings, attach
the LCP using the LCP cable. See Illustration 5.3.
24
Operating Instructions
After use, remove the LCP cable from the frequency
converter, to maintain the ingress protection class of the
enclosure.

5.3 Basic Programming

This manual explains initial set-up only. For full parameter
lists refer to the VLT
Programming Guide.
Upon initial startup the frequency converter will enter the
Start-up wizard for Open Loop Applications, see
chapter 5.3.1 Start-up Wizardfor Open Loop Applications.
Once the start-up wizard is complete, the following
additional set-up wizards and instructions are available:
For general instructions in changing parameter settings,
refer to chapter 5.3.4 Changing Parameter Settings.
5.3.1 Start-up Wizardfor Open Loop
The start-up wizard guides the installer through the set-up
of the frequency converter in a clear and structured
manner to set up an open loop application. An open loop
application does not utilise a feedback signal from the
process.
38mm
1
2
Illustration 5.4 Principle Wiring for Open Loop Start-up Wizard
Illustration 5.5 Wizard Start View
Danfoss A/S © Rev. 06/2014 All rights reserved.
®
DriveMotor FCP 106 and FCP 106
chapter 5.3.2 Set-up Wizard for Closed Loop
Applications
chapter 5.3.3 Quick Menu: Motor Set-up
chapter 5.3.5 Thermistor Set-up
Applications
FC
12
+24V
DIG IN
18
Start
19
DIG IN
20
COM DIG IN
27
DIG IN
DIG IN
29
+10V
50
+
A IN
53
A IN
54
COM
55
-
42
A OUT / D OUT
45
A OUT / D OUT
01
02
03
04
05
06
Press OK to start Wizard
Push Back to skip it
Setup 1
Reference
0-10V
MG03L202