KROHNE OPTIWAVE 5200 C/F Handbook page 58

Non-contactradar (fmcw) level meter ordistance, leveland volume measurementof liquids,pastesand slurries
Hide thumbs Also See for OPTIWAVE 5200 C/F:
Table of Contents

Advertisement

OPERATION
6
Menu
No.
2.7.2
2.7.3
2.7.4
2.7.5
2.7.6
2.8.0
2.8.1
2.8.2
2.9.0
2.9.1
2.9.2
2.9.3
1 "4-20/3.6E" is necessary for SIL 2 approval. If you make a different selection, the device does not have SIL 2 approval.
2 Units and range depend on the output function, length unit and volume unit selected. See also the table of data depen- dencies for the 4 mA settings in this section.
3 Units and range depend on the output function, length unit and volume unit selected. See also the table of data depen- dencies for the 20 mA settings in this section.
4 1.0 m/min is necessary for SIL 2 approval. If you make a different selection, the device does not have SIL 2 approval.
5 0 entries is necessary for SIL 2 approval. If you make a different selection, the device does not have SIL 2 approval.
58
Function
Function description
LENGTH UNIT
The length unit shown in normal
mode.
Conversion unit. The length, volume, mass
CONV UNIT
or flow rate conversion unit for the
conversion table and shown in normal
mode.
PSWD YES/NO
If it is necessary to protect your settings in
the supervisor menu with a password, set
this menu item to "YES".
PASSWORD
This changes the password for the
supervisor menu. Press the buttons up to 6
times in any order. This will be the new
password. To confirm the change, enter the
new password a second time.
The contrast control for the display screen.
CONTRAST
You can select a shade of grey between light
grey (level 20) and black (level
54).
CONV. TABLE
Conversion table. Use these menu items to
set up or erase conversion tables to show
length, volume or mass measurement values
in normal mode.
INPUT TABLE
The device uses the conversion table to
convert measurements to volume, mass and
flow rate readings. The readings are shown
in normal mode. Give
the number of entries on the table. Enter
the height and the related volume / mass /
flow
rate values.
DELETE TABLE
This menu item erases the data in the
conversion table.
CONFIG/RESET
Use this sub-menu to start the device
again.
SAVE
This menu item is not available.
RECALL
This menu item is not available.
RESTART
This menu item starts the device
again.
www.krohne.com
OPTIWAVE 5200 C/F
Selection list
m, cm, mm, in (inches), ft
(feet)
m3, L, gal (US gallons), ImpG
(Imperial gallons), ft3, bbl (oil
barrel), kg, t, Ston, Lton, m, cm, mm,
in, ft, m3/h, ft3/h
YES, NO
min.-max: 20...54
max. 30 entries
(distance / volume, mass
or flow rate)
YES, NO
YES, NO
YES, NO
YES, NO
03/2012 - 4001904901 - HB OPTIWAVE 5200 R01 en
Default
m
L
YES
[>], [^],
[ ], [ ],
[>] and [^]
36
0 entries
5
NO
NO
NO
NO