KROHNE OPTIWAVE 5200 C/F Handbook page 56

Non-contactradar (fmcw) level meter ordistance, leveland volume measurementof liquids,pastesand slurries
Hide thumbs Also See for OPTIWAVE 5200 C/F:
Table of Contents

Advertisement

OPERATION
6
Menu
No.
2.4.2
2.4.3
2.4.4
2.4.5
2.5.0
2.5.1
2.5.2
2.5.3
56
Function
Function description
RANGE I
This parameter sets the range of the
output current with (3.8...20.5 mA) or
without (4...20 mA) over-run values. It
also tells the device what to do if an error
occurs. For example, the device will change
to an error value of 22 mA if you set
RANGE I to 4-20/22E. If you set RANGE I to
4-20 and the device senses a measurement
error, the value will stop at the last correct
measurement.
SCALE 4mA
This gives a measurement value to 4
mA.
SCALE 20mA
This gives a measurement value to 20
mA.
ERROR DELAY
The time after which the current output
changes to an error value. The error
value shows that there is a measurement
error. mn=minutes and s=seconds.
APPLICATION
Use this sub-menu to configure the device
when there are difficult process conditions.
Only approved personnel can change these
parameters.
TANK TYPE
The conditions in which the device is used. If
the surface of the product is flat, select
"Storage". If the surface of the product is
disturbed, select "Process". If the surface
of the product is agitated with vortexes and
foam, select "Agitator".
TRACKING VEL.
Maximum tracking velocity. This value must
agree with the maximum rate of change of
the level of the liquid or solid contents in
the tank.
Er PRODUCT
The device automatically calculates the
level based on the product ε
select "TBF Partial" or "TBF Full" in menu
item 2.3.9
MEASUR.MODE, you can change the ε
value manually
to adjust readings.
. If you
r
r
www.krohne.com
OPTIWAVE 5200 C/F
Selection list
4-20, 4-20/22E, 4-20/3.6E,
3.8-20.5/22E,
3.8-20.5/3.6E
min.-max:
2
min.-max:
3
0 s, 10 s, 20 s, 30 s, 1 mn,
2 mn, 5 mn,15 mn
Storage, Process, Agitator
min-max:
0.1...10.0 m/min
min-max: 1.100 to 10.000
03/2012 - 4001904901 - HB OPTIWAVE 5200 R01 en
Default
4-20/3.6E
1
1 m / 3.28 ft
45 m /
147.63 ft
1 mn
Process
1.0 m/min
4
2.000

Advertisement

Table of Contents
loading

Table of Contents