ELECTRICAL CONNECTIONS
4
How to connect the communication cable to the remote converter
Figure 4-11: How to connect the communication cable to the remote converter
CAUTION!
Bending radius of the communication cable: ≥ 50 mm / 2
1 Remove the terminal compartment cover.
2 Remove the 4-pin connector.
3 Put the communication cable into the opening of the cable gland.
4 Put the electrical wires in the connector terminals. Tighten the terminal screws with a small slotted-tip screwdriver. Make sure
that the electrical wires agree with the terminals. For more data, refer to the electrical schema in this section.
5 Put the connector into the 4-pin socket. Attach the Faston connector (drain wire).
6 Attach the terminal compartment cover.
7 Tighten the cable gland. Make sure that the remote converter is correctly sealed.
36
¨
www.krohne.com
OPTIWAVE 5200 C/F
03/2012 - 4001904901 - HB OPTIWAVE 5200 R01 en