5 SETUP AND PREPARATION

5.1.3 When using both the master and slave functions

Perform hardware test. (Mode 9)
Set node No.
Set mode to 6, 7, or 8.
Connect DeviceNet cable to QJ71DN91.
Use GX Configurator-DN?
Auto configuration *1
Execute auto configuration. Not needed when setting
parameters for master function manually.
Parameters for master function
Set parameters for master function.
Parameters for slave function
Set parameters for slave function.
Not needed unless I/O points for slave function are
changed.
Auto communication start setting
Set auto communication start setting. Not needed when starting
I/O communication by I/O Communication Request (Y11).
Saving parameters to flash ROM
Save parameters to flash ROM.
Refresh setting
Configure auto refresh settings. Write intelligent
function module parameters to CPU module.
Programming for control
Create sequence program for control. After writing it to
programmable controller, reset CPU module.
5 - 3
Refer to Chapter 7 for programming for the master function, and Chapter 8 for
programming for the slave function.
Start
Not use
Use
Failed
Test run
OK
Operation
*1: Check that power supplies to slave nodes and network are ON and the wiring is correct.
(See Section 5.4.)
(See Section 5.3.2.)
(See Section 5.3.3.)
(See Section 5.5.)
Auto configuration *1
Create sequence program for executing auto
configuration. Not needed when setting parameters for
master function manually.
Parameters for master function
Create sequence program for setting parameters for
master function.
Parameters for slave function
Create sequence program for setting parameters for
slave function. Not needed unless I/O points for slave
function are changed.
Auto communication start setting
Create sequence program for auto communication
start setting. Not needed when starting I/O
communication by I/O Communication Request (Y11).
Saving parameters to flash ROM
Create sequence program for saving parameters to
flash ROM.
Refresh setting
Create sequence program for refresh.
Programming for control
Create sequence program for control. After writing it to
programmable controller, reset CPU module.
Set Request for Saving Parameters to Flash ROM
(Y17) to ON to save parameters to flash ROM.
MELSEC-Q
Failed
Test run
OK
5 - 3