Mitsubishi Electric QJ71DN91 User Manual page 70

Melsec system q programmable controller devicenet master-slave module gx configurator-dn
Hide thumbs Also See for QJ71DN91:
Table of Contents

Advertisement

3 SPECIFICATIONS
3 - 45
(2) Hardware Test Result Area (address: 062F
The hardware or communication test result is stored.
Error code
0000
No error
H
60AA
RAM error
H
61AA
ROM error
H
62AA
CAN controller check error
H
Network power supply
63AA
H
error
70AA
H
71AA
H
Microcomputer error
72AA
H
73AA
H
74AA
H
Error code
Error
Node No.
0001
H
duplication error
0002
Bus off error
H
Network power
0003
H
supply error
0004
Communication
H
0005
error
H
0006
No error
H
Table 3.31 Hardware test results
Error
Hardware test completed normally.
Hardware failure. Please consult your local Mitsubishi
service center or representative, explaining a detailed
description of the problem.
Verify that power is supplied to the network.
Hardware failure. Please consult your local Mitsubishi
service center or representative, explaining a detailed
description of the problem.
Table 3.32 Communication test results
Detail
Any other node on the network
has the same node No. as the
own node.
A bus off occurred during the
test.
The network power supply is
OFF.
Data could not be sent or
received correctly.
Communication test was
completed normally.
MELSEC-Q
/1583)
H
Action
Action
• Assign unique node numbers to all nodes on
the network.
• Set the same communication speed value to all
nodes on the network.
• Check the overall network for disconnection of
terminating resistors, DeviceNet cable length,
etc.
• Turn ON the network power supply.
• Connect one or more nodes to the network.
• Set the same communication speed value to all
nodes on the network.
• Check the overall network for disconnection of
terminating resistors, DeviceNet cable length,
etc.
3 - 45