7 PROGRAMMING FOR EXECUTING THE MASTER FUNCTION
7 - 5
(b)
Settings of the slave nodes
For the setting of node No. and communication speed, refer to the manual
for each slave node.
1)
1st slave node
(Omron's CompoBus/D, 8-point input (DRT1-ID08))
Item
Node No.
Communication speed
Connection type
I/O points
2)
2nd slave node
(Omron's CompoBus/D, 8-point output (DRT1-OD08))
Item
Node No.
Communication speed
Connection type
I/O points
3)
3rd slave node (QJ71DN91(slave node))
Item
Node No. (Node No. switches)
Communication speed (Mode switch)
Connection type
Slave function receive-bytes (input points)
Slave function transmit-bytes (output points)
4)
4th slave node
(Rockwell Automation's Flex I/O DeviceNet adapter + 16-point input
(1794ADN + IB16))
Item
Node No.
Communication speed
Connection type
I/O points
MELSEC-Q
Setting
Node No.1
125kbaud
Polling
8 input points
Setting
Node No.2
125kbaud
Polling
8 output points
Setting
Node No.4 (04)
125kbaud (Mode 3)
Polling
8 bytes
8 bytes
Setting
Node No.3
125kbaud
Bit strobe
16 input points