Mitsubishi Electric QJ71DN91 User Manual page 85

Melsec system q programmable controller devicenet master-slave module gx configurator-dn
Hide thumbs Also See for QJ71DN91:
Table of Contents

Advertisement

4 FUNCTIONS
4 - 12
(3) Operation flow
This section explains how I/O communication is performed with the master node.
(a)
When starting I/O communication by I/O Communication Request (Y11)
Module Ready (X0F)
Auto Configuration
Request (Y15)
Request for Saving
Parameters to Flash
ROM (Y17)
I/O Communication
Request (Y11)
I/O Communicating
(X01)
Error Set Signal for
Slave Function (X08)
Error Information for
Slave Function (0601
)
H
Parameters for Slave
Function (060E
, 060F
)
H
H
Slave Function Receive
Data (0B00
to 0B3F
)
H
H
Slave Function Transmit
Data (0C00
to 0C3F
)
H
H
1)
Set parameters in Parameters for Slave Function (address: 060E
060F
H
2)
In Slave Function Transmit Data (address: 0C00
values of ON/OFF information to be sent to the master node.
3)
Set Auto Configuration Request (Y15) and Request for Saving
Parameters to Flash ROM (Y17) to OFF.
4)
When I/O Communication Request (Y11) is set to ON, the parameters
are checked.
5)
When the parameter check is succeeded, I/O communication with the
master node is started and I/O Communicating (X01) is set to ON.
Note that, until receiving an I/O communication request from the
master node, the module waits for connection establishment.
• Data sent from the master node are stored in Slave Function
Receive Data (address: 0B00
• The ON/OFF information to be sent to the master node is set in
Slave Function Transmit Data (address: 0C00
6)
If the parameter check has failed, the ERR. LED lights up and Error
Set Signal for Slave Function (X08) is set to ON. At this time, I/O
Communicating (X01) is not set to ON.
Check the error code in Error Information for Slave Function (address:
0601
), and take corrective actions.
H
7) Setting I/O Communication Request (Y11) to OFF stops I/O
communication with the master node, causing I/O Communicating
(X01) to turn OFF.
OFF
3)
OFF
3)
1)
MOV/TO
instruction
2)
MOV/TO
instruction
).
4)
5)
6)
MOV/FROM
instruction
Parameter
check
to 0C3F
H
to 0B3F
).
H
H
to 0C3F
H
MELSEC-Q
7)
MOV/FROM
instruction
MOV/TO
instruction
,
H
), set initial
H
).
H
4 - 12

Advertisement

Table of Contents
loading

Table of Contents