Applicable Systems - Mitsubishi Electric QJ71DN91 User Manual

Melsec system q programmable controller devicenet master-slave module gx configurator-dn
Hide thumbs Also See for QJ71DN91:
Table of Contents

Advertisement

2 SYSTEM CONFIGURATION

2.2 Applicable Systems

Applicable CPU module
CPU type
Basic model
QCPU*
High
Performance
model QCPU
Programmable
controller CPU
Process CPU
Redundant CPU
Universal model
QCPU*
2 - 3
This section describes the systems to which the QJ71DN91 can be applied.
(1) Applicable modules and base units, and No. of modules
(a)
When mounted with a CPU module
The table below shows the CPU modules and base units applicable to the
QJ71DN91 and quantities for each CPU model.
Depending on the combination with other modules or the number of
mounted modules, power supply capacity may be insufficient.
Pay attention to the power supply capacity before mounting modules, and if
the power supply capacity is insufficient, change the combination of the
modules.
CPU model
Q00JCPU
Q00CPU
3
Q01CPU
Q02CPU
Q02HCPU
Q06HCPU
Q12HCPU
Q25HCPU
Q12PHCPU
Q25PHCPU
Q12PRHCPU
Q25PRHCPU
Q02UCPU
Q03UDCPU
3
Q04UDHCPU
Q06UDHCPU
*1: Limited within the range of I/O points for the CPU module
*2: Can be installed to any I/O slot of a base unit.
*3: Use the QJ71DN91 whose serial No. (first five digits) is 03052 or later.
(b)
Mounting to a MELSECNET/H remote I/O station
The QJ71DN91 cannot be mounted to any MELSECNET/H remote I/O
station.
Mount it to a CPU module on a master station.
*1
No. of modules
Up to 8
Up to 24
Up to 64
Up to 64
N/A
Up to 36
Up to 64
MELSEC-Q
2
Base unit*
Main base unit
Extension base unit
: Applicable,
: N/A
2 - 3