When There Is A Communication Error Between Master Station And Aj65Bt-68Td - Mitsubishi Electric AJ65BT-68TD User Manual

Thermocouple temperature input module
Table of Contents

Advertisement

6. TROUBLESHOOTING
6.6
When There is a Communication Error between Master Station
and AJ65BT-68TD
"ERR." LED of master
station flickers
Do the
parameter setting
and loading system
configuration
match?
Y
Is the
master station
link special register
SW0080 to SW0083 (other
station data link
status) turned
ON?
Y
Is the
master station
link special register
SW0098 to SW009B
(duplicate station
number status)
turned ON?
Y
Check the module whose
SW0098 to SW009B is ON
Is the station
number switch set
correctly?
Y
Corresponding module failure
Downloaded from
ManualsNet.com
If the station number duplicate bit is turned on in the link special register SW0098 to SW009B
(duplicate station number status), check the corresponding station number of AJ65BT-68TD using the
following flow.
Troubleshooting flow when "ERR" LED of master station is flickering
N
Correct parameter setting or
loading system configuration
N
Master station failure
N
Check the module whose
SW0080 to SW0083 is ON
N
Set the station number
switch correctly
Restart the power supply/
Turn on the reset switch
To the next page
search engine
N
Is power supply
turned ON?
Turn the power ON
Y
N
Is "POWER"
LED lit?
Y
Is the supplied
voltage within the
specified range?
Y
Corresponding module failure
N
Is "RD" LED lit?
Are
Y
communication
cables connected
correctly?
Y
Corresponding module failure
To the next page
6-4
MELSEC-A
Check on the master side
Check on the AJ65BT-68TD side
N
Set the supplied voltage
within the specified range
N
*1
Correct the wiring of
communication cables
To the next page