Verifying Storedge Components Functionality - SolarEdge StorEdge Installation Manual

For smart energy management using lg chem batteries
Hide thumbs Also See for StorEdge:
Table of Contents

Advertisement

Verifying StorEdge Components Functionality

 5. To set up the level of charging from AC, do the following:
 a. Select Energy Manager  Storage Control. The following is displayed:
B a c k u p
A C
 b. Select AC Charge Li  Limit Type, and set one of the following limits:
Set %PV to enter a limit as a percentage of year-to-date energy production.
Set kWh to enter a fixed annual energy limit.
Set None to unlimit the charging.
 6. To set a minimum battery level used for backup, so that the battery will always have energy stored in
case backup power is needed, select Backup Rsvd and set the required level of reserved energy as 
percentage of the battery capacity
For backup power + Smart Energy Management - according to user requirement
 
o
For backup-only - according to battery manufacturer recommendation, if provided.
 
o
Verifying StorEdge Components Functionality
Upon installation and configuration completion, the system should be operating according to the 
selected StorEdge application.
This section describes how to verify that all system components are functioning as expected.   I f not, refer 
to Troubleshooting on page 92. 
To check the battery:
The test is available in CPU version 3.24xx and later (but not in version 4.x.xxx).
If two batteries are installed, the active battery will be tested first, and then the standby battery. If the
active battery fails the test, the test will stop and the standby battery will not be tested.
1. Verify that AC is ON.
2. Turn the inverter ON/OFF switch to ON.
3. Make sure the Connection Unit is ON.
4. Enter Setup mode and select Maintenance StorEdge Self-TestStart Test. The battery charges
and discharges within approximately two minutes to check performance.
During the test, the following message is displayed:
S h o r t
P r o g r e s s . . .
A n y
b u t t o n
Upon the test completion, the following message is displayed:
S e l f - t e s t
s u c c e s s f u l l y
A n y
b u t t o n
88
R s v d
< N / A >
C h a r g e
L i < N o n e >
T e s t
i n
t o
s t o p
c o m p l e t e d
t o
c o n t .
StorEdge Inverter Installation Guide MAN-01-00390-1.1