Operation METPOINT® BDL compact
Main menu Settings Sensor settings A1 Right arrow (2
The remaining text fields can be marked in the same manner as is described here, in Chapter
12.2.2.7 Marking and setting text
Main menu Settings Sensor settings A1 Right arrow (2
BEKO-Digital
20.00
See also Chapter
12.2.2.1 Selection of the sensor type (Example type: CS digital sensor)
Note:
After having confirmed with
cepted.
Caution:
Reference temperature and reference pressure (setting ex works 20°C, 1000 hPa):
All the volume flow (m³/h) and consumption values (m³) that are indicated on the display refer to
20°C and 1000 hPa (according to ISO 1217 suction condition).
Alternatively, 0°C and 1013 hPa (=standard cubic meter according to DIN 1343) can also be en-
tered as the reference. Under no circumstances must the operating pressure or the operating
temperature be entered into the reference conditions!
METPOINT® BDL compact
fields!
100.00
1000.00
ltr
OK,
the lettering returns to black and the values and settings are ac-
page) Text field gas constant
nd
A preset selection of suitable
nd
page)
The text fields with red letters show that dif-
ferent values, such as the
name,
were changed or added.
gas
constants.
diameter
and the
47