Page 1
EN - English Instructions for installation and operation Data logger METPOINT BDL compact ®...
Page 2
Pictograms and symbols Dear customer, ® Thank you for deciding in favour of the METPOINT BDL compact. Please read these installation and oper- ating instructions carefully before mounting and starting up the device and follow our directions. Perfect func- tioning and safe operation of the BDL can only be guaranteed when the provisions and notes stipulated here are strictly adhered to.
Settings ................................36 14.3.1 Password setting ..............................36 14.3.2 Sensor settings ..............................37 14.3.2.1 Selection of the sensor type (example: BEKO digital sensor type) ............ 37 14.3.2.2 Denoting the measuring data and determining the resolution of the decimal places ......40 14.3.2.3 Recording measuring data .........................
Page 4
Pictograms and symbols 14.3.2.9.2 Modbus settings ........................ 54 ® 14.3.2.9.3 Modbus settings for the METPOINT SD23 ..............58 14.3.3 Device settings ..............................60 14.3.3.1 Language ............................61 14.3.3.2 Date & time ............................61 14.3.3.3 Network settings ..........................62 14.3.3.4 ModBus (slave) ..........................63 14.3.3.5 Relay settings ...........................
Pictograms and symbols Pictograms and symbols General danger symbol (danger, warning, caution) General note Observe the installation and operating instructions (on the type plate) Observe the installation and operating instructions Signal words in accordance with ISO 3864 and ANSI Z 535 Danger! Imminent hazard Consequences of non-observance: serious injury or death...
If you have any queries regarding these installation and operating instructions, please con- tact BEKO TECHNOLOGIES. Warning! Risk of injury in the event of insufficient qualifications! Improper use can lead to significant personal injury and material damage.
BDL compact. An alarm message can be sent via SMS or e-mail in is possible with the METPOINT connection with the BEKO METPOINT connect software. With the 3.5" colour display with a touch panel, all of the information is visible at a glance. Operation is very easy.
Proper use Proper use ® METPOINT BDL compact data logger serves for the stationary measured data acquisition and storage of analogue and digital input signals. ® The METPOINT BDL compact data logger is exclusively designed and constructed for the proper application purpose that is described herein and must only be used correspondingly.
Despite all due care and attention, transport damage cannot be excluded. Therefore, check the ® METPOINT BDL compact for possible transport damage subsequent to transport and removal of the packaging material. The forwarding agent and BEKO TECHNOLOGIES or the BEKO TECHNOLOGIES agency shall be informed immediately about any kind of damage. Warning! Overheating! Overheating will destroy the evaluation unit.
SDI interface (Serial Data Interface) 4 (2x2) sensor inputs for analogue and digital sen- Sensor inputs sors, freely assignable Analogue signals: 0/4 - 20 mA, 0 - 1/10/30 V Pulse signals Sensor signals Pt100, Pt1000 Digital signals: RS485, BEKO-SDI METPOINT® BDL compact...
Page 11
Technical data BDL compact Technical data 2 pieces potential-free change-over contacts Alarm outputs (alarm relays) Freely programmable, alarm management As regards sensors with an internal signal output, the analogue output and pulse output are looped Analog output and pulse output through, e.g.
Page 12
Operating temperature: -30 … +60°C BEKO sensors Digital BEKO sensors for the pressure dew point with an RS485 interface, series: DPM SD23 Digital BEKO sensors for the dew point and consumption with an SDI interface, series: DP 109, DP 110, FS 109, FS 211 Analogue BEKO sensors for the pressure, temperature, clip-on ammeter pre-configured Sensors with analogue signals: 0/4 –...
Page 13
Technical data BDL compact CE conformity EMC Directive 2004/108/EC Low-Voltage-Directive 2006/95/EC ROHS II Directive 2011/65/EU EMC interference immunity, industrial field EN 61326-1 & EN 61326-2-3 EMC interference emission, group 1, class B EN 61326-1 Safety provisions for electrical equipment for measurement, EN 61010-1 control, and laboratory use CE labelling according to the 2006/95/EG Low-Voltage-Directive...
Dimensions Dimensions The device can either be integrated into an equipment cabinet or fixed on the wall using suitable dowels and screws. Details can be found in the following drawings. Dimensions for wall mounting NOTE! The wall mounting must withstand four times the weight of the device (10.8 kg). Dimensions for the mounting of the instrument panel METPOINT®...
Page 15
Dimensions Cutout for the mounting of the instrument panel METPOINT® BDL compact...
Installation 10 Installation 10.1 Safety instructions Danger! Supply voltage! The contact with non-insulated parts carrying supply voltage involves the risk of an electric shock resulting in severe injuries and death. Measures: • Observe all regulations in effect during the electrical installation (e.g. VDE 0100)! •...
Page 17
Installation The plug of the power supply cord is used as a separator. This separator must be clearly recognisable and easily accessible by the user. A plug connector with a CEE7/7 system is necessary. All the electrical lines carrying supply voltage or another voltage that is dangerous in the case of con- tact (power supply cord, alarm and indicator relays), must additionally be equipped with double or rein- forced insulation (EN 61010-1).
Installation 10.1.1 Prevention of electrostatic discharge (ESD) Danger! Damage through ESD possible The device contains electronic components which may be sensitive to electrostatic discharge (ESD). The contact with electrostatically-charged persons or objects compromises these compo- nents. In the worst case, they are immediately destroyed or will fail subsequent to the start-up. Observe the requirements stipulated in EN 61340-5-1 to minimise or prevent the possibility of damage through sudden electrostatic discharge.
Installation 10.2 Instructions regarding the installation 10.2.1 Degree of protection through the housing (IP code) ® The METPOINT BDL compact data logger meets the requirements of the IP 44 degree of protection in accordance with EN 60529. The degree of protection of a housing is defined by the IP code and a two-digit code number. The first digit includes the protection for persons and resources while the second digit only refers to the protection against water.
Connection/terminal diagram METPOINT® BDL compact ® 11 Connection/terminal diagram METPOINT BDL compact View of the connecting plugs at the back of the device. All of the connections at the back of the device are designed as pluggable screw terminal blocks. For the connection, the following needs to be observed: •...
Connection/terminal diagram METPOINT® BDL compact 11.2 Pin assignment plug "A1 – B2" (analogue and digital channels) Jumpers are internally available on both boards Depending on the selected version, the following combinations are possible: Combination Channel D = digital channel A = analogue channel Pin assignment connector "D"...
Connection/terminal diagram METPOINT® BDL compact 11.4 Pin assignment connector "E" (RS485 -- Modbus) 11.5 Pin assignment Connectors "A – B" (alarm relay) The alarm outputs are designed as potential-free change-over contacts. Via the potential-free contacts, the alarm signal can be transmitted, e.g. to a control centre. The connecting plugs of the alarm contacts are marked with "A"...
Page 23
Connection/terminal diagram METPOINT® BDL compact View of the connecting plugs at the back of the device. Potential-free alarm change-over contacts, connecting plugs A and B / AW G 16 - AW G 28 Line cross-section: 0.14 – 1.5 mm 1 = NC = Normally Closed 2 = COM 3 = NO = Normally Open CAUTION!
4 – 20 mA for further processing . In the connection diagrams, the collec- tion of the current signal for an external PLC/central control system or for an external display is ex- plained. When using the connecting leads BEKO 4014064 or 4014065, the following pin assignment needs to be observed: SD21...
Connection diagrams of the different sensor types 4014065 (10m) The following connection diagrams in Chapter 10 apply from A1 to B2! DP/SD series: dew point sensors from BEKO TECHNOLOGIES FS series: consumption sensors from BEKO TECHNOLOGIES 12.1 Connection dew point sensors DP 109 series ®...
Connection diagrams of the different sensor types 12.2 Connection consumption/dew point sensors DP/FS series ® METPOINT BDL compact DP 110 FS 211 FS 109 The digital data transmission between ® the METPOINT BDL compact and the sensors DP 110, FS109, and FS 211 is implemented via the SDI bus line.
Page 27
Connection diagrams of the different sensor types Externally required R = 4K7 Caution: Counts one unit of con- sumption when switch- ing on the ® METPOINT BDL com- pact Externally required R = 4K7 Connection impossible! METPOINT® BDL compact...
Connection diagrams of the different sensor types 12.3 Analogue 2-wire, 3-wire, and 4-wire current signal Sensors with 4 - 20 mA output in 2-wire technology ® METPOINT BDL compact ® METPOINT BDL compact with an external trans- mission Ensure that the electric circuit is closed in any case. (e.g.
Page 29
Connection diagrams of the different sensor types Sensors with a 0/4 – 20 mA output in 3-wire technology ® METPOINT BDL compact ® METPOINT BDL compact with an external transmission Ensure that the electric circuit is closed in any case. METPOINT®...
Page 30
Connection diagrams of the different sensor types Sensors with 0/4 – 20 mA output in 4-wire technology ® METPOINT BDL compact ® METPOINT BDL compact with an external trans- mission Ensure that the electric circuit is closed in any case. METPOINT®...
Connection diagrams of the different sensor types 12.4 3 and 4-wire voltage supply 0 - 1/10/30 VDC Sensors with a voltage output in 3-wire technology Sensors with a voltage output in 4-wire technology METPOINT® BDL compact...
Connection diagrams of the different sensor types 12.5 2, 3, and 4-wire terminal assignment of PT100/PT1000/KTY81 2-wire PT100/PT1000/KTY81 3-wire PT100/PT1000/KTY81 4-wire PT100/ 1000/KTY81 12.6 Assignment with RS485 such as SD23 Sensor with an RS485 interface, e.g. SD23 METPOINT® BDL compact...
Connecting the METPOINT® BDL compact with a PC ® 13 Connecting the METPOINT BDL compact with a PC Important: ® The IP addresses of the PC and METPOINT BDL compact must be provided statically (DHCP off) and they must be in the same network. ®...
Operation METPOINT® BDL compact ® 14 Operation METPOINT BDL compact The operation is self-explanatory to the largest possible extent and is menu-driven via the touch panel. The selection of the respective menu items is realised via short "tapping" with the finger or using a soft- pointed pen.
Operation METPOINT® BDL compact 14.2.1 Main menu subsequent to the switching-on Hard- and soft- Alarm indica- Status data Interval data logger and re- Date and ware version tion logger maining storage space time Important: Prior to carrying out the first sensor settings, the language and time should be set. Note: Chapter 12.2.4.1 Language...
Operation METPOINT® BDL compact 14.3 Settings All settings are password-protected! Settings or changes must generally be confirmed by OK! Note: When returning to the main menu and calling again one of the setting menus afterwards, the password must be re-entered! Main menu ...
Operation METPOINT® BDL compact 14.3.2 Sensor settings Important: Sensors from BEKO TECHNOLGIES are generally pre-configured and can be directly connected to a free sensor channel! Main menu Settings Sensor settings After having entered the password, an overview of the available channels will appear.
Page 38
Operation METPOINT® BDL compact Main menu Settings Sensor settings A1 Text field type BEKO digital Now, the Type BEKO digital is selected for the VA/FA 400 series and confirmed by OK. page) Text field diameter Main menu ...
Page 39
Operation METPOINT® BDL compact Main menu Settings Sensor settings A1 BEKO-Digital 0,00 ltr/min Now, a name can be entered. 2345678 0,00 Main menu Settings Sensor settings A1 Name BEKO-Digital Air-1 0,00 ltr/min Subsequent to marking and confirming by OK, the configuration of the sensor is completed.
(0 to 5 dec- imal places). See Chapter 12.2.2.7 Marking and setting text fields 14.3.2.3 Recording measuring data Main menu Settings Sensor settings A1 Recording button BEKO-Digital 0.000 With the recording buttons, the measuring data ltr/min are selected which will be stored at an acti- vated data logger.
Operation METPOINT® BDL compact 14.3.2.4 Alarm settings Main menu Settings Sensor settings A1 Alarm button By pressing an alarm button, the following window will appear: In the alarm settings, an alarm-1 alarm-2 incl. hysteresis can be entered for each channel. Via the alarm overview menu item (via the main...
Page 42
Delay time T0 cannot be changed and is an im- mediate alarm. Please confirm with OK. Main menu Settings Sensor settings A1 Name BEKO-Digital 0,00 ltr/min Subsequent to the alarm activation at channel 2345678 0,00 The settings are completed by means of the buttons! METPOINT®...
293.0 1000.0 Note: 110.0 advanced setting is only available for BEKO digital. 200.000 The settings are completed by means of the buttons! Note: After having confirmed by the lettering is switched to black again. The values and settings have been accepted.
Main menu Settings Sensor settings B1 Second step: Select type BEKO Digital Main menu Settings Sensor settings B1 Type text field BEKO digital Third step: confirm twice with Now, you can determine a...
Page 45
Operation METPOINT® BDL compact BEKO-Digital By pressing on fields with a white back- ground, changes or entries can be made. 100.00 1000.00 20.00 alarm (see Chapter 12.2.2.4 Alarm settings) recording buttons (see Chapter 12.2.2.3 Recording measuring data), the resolution of the decimal places and the...
Page 46
Operation METPOINT® BDL compact Main menu Settings Sensor settings A1 Text field unit A preset selection of suitable units. Main menu Settings Sensor settings A1 Right arrow (2 page) Text field diameter Important: Here, the inner diameter...
Page 47
12.2.2.7 Marking and setting text fields! Main menu Settings Sensor settings A1 Right arrow (2 page) The text fields with red letters show that dif- BEKO-Digital ferent values, such as the diameter and the name, were changed or added.
BDL compact. Variants with an assembled analog board are possible. Short overview of the possible Type settings including examples. For BEKO-Digital, see Chapter 12.2.2.1 Selection of the sensor type (example BEKO-Digital sensor type) 12.2.2.6 Dew point sensor with the BEKO-DIGITAL type.
Page 49
Operation METPOINT® BDL compact With the Set-value-to button (offset), the measured data of the sensor can be set to a certain value. The positive or negative difference of the off- is indicated. With the reset button, the offset can be reset to zero.
Operation METPOINT® BDL compact Main menu Settings Sensor settings B1 Type text field 0/4-20mA Here, for example, Type 4 – 20 14.3.2.8.2 Type PT100x and KTY81 Main menu Settings Sensor settings B2 Type text field PT100x Name 0,00 ltr/min...
Operation METPOINT® BDL compact 14.3.2.8.3 Type pulse (pulse value) Main menu Settings Sensor settings B2 Type text field Pulse Normally, the numerical value with the unit Name stands for 1 pulse on the sensor and can di- rectly be entered into the 1 pulse = text field.
Page 52
Operation METPOINT® BDL compact Main menu Settings Sensor settings B2 Right arrow (2 page) Consumption m³/h m³/h m³/min Units for the current consumption for the pulse type. Note: Example with the unit cubic metre! Main menu Settings Sensor settings B2 Right arrow (2 page) ...
Operation METPOINT® BDL compact 14.3.2.8.4 Type no sensor Main menu Settings Sensor settings A2 Type text field No sensor Serves to declare a channel which is currently not required as configured. When returning from Type no sensor to sensor settings, the channels are displayed as free.
Operation METPOINT® BDL compact 14.3.2.9 Type Modbus 14.3.2.9.1 Selection and activation of the sensor type First step: select a free sensor channel Main menu Settings Sensor settings A1 Second step: select the Modbus type Main menu Settings Sensor settings A1 Type text field Modbus Third step: confirm with Now, a name...
Page 55
Operation METPOINT® BDL compact The sensor provides the measured values in registers. The values can be located and read out by the BDL compact via Modbus. For this purpose, the desired register ad- dresses need to be set in the BDL compact. The entry of the register/data address is im-...
Page 56
Operation METPOINT® BDL compact Holding register - UI1(8b) - numerical value: 18 Selection register type Holding register, data type U1(8b) and byte order A / B Hbyte Lbyte 18 => Data order 1. byte 2. byte Holding register – UI4(32) - numerical value: 29235175522 AE41 5652 Selection register type Holding register,...
Page 57
Operation METPOINT® BDL compact Main menu Settings Sensor settings A1 Scal. text field The application of this factor allows for the ad- justment of the output value by the latter. Main menu Settings Sensor settings A1 OK By pressing the button, the specifications are accepted and stored.
Operation METPOINT® BDL compact 14.3.2.9.3 Modbus settings for the METPOINT SD23 ® ® When connecting the METPOINT SD23 via Modbus, the following settings are required: First step: select a free sensor channel Main menu Settings Sensor settings Select a free channel (example: channel A1) Second step: select Modbus type Main menu ...
Page 59
Operation METPOINT® BDL compact Fifth step: define the register Main menu Settings Sensor settings A1 Va Use The definition of other registers is imple- mented in the same manner. The settings of the reg./data format are the same for all the registers.
Operation METPOINT® BDL compact 14.3.3.1 Language Main menu Settings Device settings Language Here, one out of 10 languages can be selected for the METPOINT ® BDL compact. 14.3.3.2 Date & time Main menu Settings Device settings Date & time By pressing the Time zone text field and entry...
Operation METPOINT® BDL compact 14.3.3.3 Network settings Main menu Settings Device settings Network settings Here, a connection to a computer can be set up and established, with or without DHCP. Note: With an activated DHCP (green tick), the au- ®...
Operation METPOINT® BDL compact 14.3.3.4 ModBus (slave) With the RS485 ModBus interface, customer-specific systems (GLT, SPS, Scada) can be connected ® with the METPOINT BDL compact. Main menu Settings Device settings ModBus settings Here the transmission parameters Modbus ID, baud rate, stop bit and parity must be set.
Operation METPOINT® BDL compact 14.3.3.5 Relay settings Main menu Settings Device settings Relay settings When activating the Relay buttons, it is possible to allow for a relay cut-off by means of the indicated alarm message. Settings are only possible in the password-pro- tected menu.
Operation METPOINT® BDL compact 14.3.3.7 System Overview of the system settings Important: Prior to the update, save the device settings on a USB stick! Note: The button with the yellow background indicates which update option is available. 14.3.3.7.1 System update Main menu ...
Operation METPOINT® BDL compact 14.3.3.7.3 Check for available updates (USB) Main menu Settings Device settings System update Check USB stick for available updates When, after having pressed the Check USB stick for available updates button, the follow- ing messages appear in the window, the ®...
Operation METPOINT® BDL compact Main menu Settings Device settings System System update Update channels Update for the channels of the METPOINT® BDL compact. Important: If, subsequent to the channel update, the Restart button appears, it must be pressed to restart the ®...
Operation METPOINT® BDL compact 14.3.3.7.5 Reset factory defaults Main menu Settings Device settings System Reset factory defaults If required, the BDL can be re-booted by pressing the Restart button. 14.3.3.8 Calibrating the touch screen Main menu Settings Calibration touch screen If required, the screen calibration can be changed here.
Operation METPOINT® BDL compact 14.3.4 Brightness Main menu Settings Brightness Here, the desired brightness (15 … 100%) of the display can directly be set. E.g.: brightness to 50%. Zum .Beispiel: Helligkeit auf 50% By means of the Darken-after button, the brightness can be reduced to a minimum at the...
Operation METPOINT® BDL compact 14.3.6 System overview Main menu Settings System overview system overview menu item provides information on the applied voltages and cur- rents of the individual and the entire chan- nels, as well as on the voltage supply of the power supply units.
Operation METPOINT® BDL compact 14.3.8.1 Activate the option "virtual channels" After having acquired the "virtual channels" option, the latter needs to be activated first. Main menu Settings Via METPOINT ® BDL compact D By pressing the button for "virtual chan- nels", you will be requested to enter the activa- tion code.
Operation METPOINT® BDL compact 14.3.8.3 Selection of the sensor type Main menu Settings Sensor settings Virtual channels V1 If no sensor was configured yet, the Type no sensor will appear. Pressing the text field Type no sensor will en- able you to go to the selection list of sensor types (see next step).
Operation METPOINT® BDL compact 14.3.8.4 Configuration of the individual virtual values Per each individual channel, up to eight virtual values can be calculated which need to be activated separately: 14.3.8.4.1 Activation of the individual virtual values Main menu Settings Sensor settings Virtual channels V1 Right arrow (2 page) ...
Operation METPOINT® BDL compact By pressing the desired channel button, e.g. A1b, the selection is accepted. If the Const. value button was pressed, the value needs to be determined via the numeric keypad. By pressing the button, the value is accepted. ...
Operation METPOINT® BDL compact 14.3.8.4.4 Definition unit Main menu Settings Sensor settings Virtual channels V1 Right arrow (2 page) Unit By pressing the text field Unit, a list with the available units will appear. The selection of the unit is implemented by pressing the desired unit button.
Operation METPOINT® BDL compact Define the unit and accept with OK. By means of buttons Clr, the entry can be corrected. Button erases the last character Button erases the entire value Important Important When all of the values and operators are applied, calculations with three values and 2 oper- ands are possible, which are solved according to the following formula: Example: V1a = (1...
Page 77
Operation METPOINT® BDL compact Main menu Settings Sensor settings Virtual channels V1 Recording button With the Recording buttons, the measuring data are selected which are stored at an activated data logger. Caution: Prior to recording the selected measuring data, the data logger must be activated subsequent to the completion of the settings (see Chapter 12.2.1.2 Logger settings (data logger) See also Chapter...
Operation METPOINT® BDL compact 14.3.8.6 Example calculation "specific performance" As an example, a compressor plant with three compressors is taken as the basis. Consumption measurement in each case with an FS109 consumption probe at inputs A1 - B1, and an electric meter at input B2. The total consumption of air and energy, and the "specific performance"...
Page 79
Operation METPOINT® BDL compact Result is the power consumption read from the electric meter 66090.2 m³ V1a total compressed-air consumption V1b power consumption 4720.75 KWh Here, the calculation of the specific performance is implemented with V1b/V1a with 0.072 KWh/m³ as the result. 66090.2 m³...
Operation METPOINT® BDL compact 14.3.9 Analogue total (optional) The "analogue total" option offers the possibility of a consumption determination also for sensors with analogue outputs, e.g.: 0-1/10/30 V or 0/4 – 20 mA. 14.3.9.1 Activating the "analogue total" option Subsequent to the acquisition of the "analogue total" option, the latter first needs to be activated. Main menu ...
Operation METPOINT® BDL compact Main menu Settings Sensor settings B1 Type text field Selection of the required sensor type by press- ing the respective button, here, for example 4- 20 mA. Confirmation and acceptance with the but- ton.
Operation METPOINT® BDL compact 14.3.10.1 Activating the "web server" option Main menu Settings Via METPOINT ® BDL compact By pressing the button for "analog total ", you will be requested to enter the activation code. Enter Code für Option 3 Please enter your activation code into the text field and activate it by pressing the button.
Operation METPOINT® BDL compact 14.3.11 Data logger settings Main menu Settings Logger settings In the uppermost row, the pre-defined time in- tervals 1, 2, 5, 10, 15, 30, 60, and 120 sec- onds can be chosen for the recording. A deviating individual time interval can be en-...
Page 86
Operation METPOINT® BDL compact Main menu Settings Logger settings Enforce-new-logger-file button Main menu Settings Logger settings Force-new-record-file button Comment text field By pressing the Force-new-record-file button, a new recording file is created, and with the selection of the Comment text field, a name or...
Page 87
Operation METPOINT® BDL compact Main menu Settings Logger settings Stop time button By pressing the Stop time button and subse- quently pressing the date/time text field be- low, the date and the time for the end of the data logger recording can be set.
Page 88
Operation METPOINT® BDL compact Main menu Settings Logger settings Start time button/Stop time button Date/time text field Cal button By means of the button, the desired date can easily be chosen from the calen- dar. Main menu ...
Operation METPOINT® BDL compact 14.4 Graphics Main menu Graphics Caution: In the graphics, only those records can be displayed which are already completed! The currently running recordings can be observed in graphics/current values. (see Chapter 12.4 Graphics/current values) During the running measurement, no values are displayed! Zoom and scroll possibilities in the time range of the graphics: Maximally, an entire day can be displayed (24h).
Page 90
Operation METPOINT® BDL compact Main menu Graphics Date text field By pressing the Date text field, the calen- dar will appear, from which the suitable date can easily be selected. Here, the stored measuring data can be selected according to the time (start stop), comment,...
Page 91
Operation METPOINT® BDL compact Main menu Graphics Set-up Unit text field Here, the unit of the record to be displayed is selected from the menu. Main menu Graphics m³/h Now, the y-axis scaling with min, max, and grid can be set.
Operation METPOINT® BDL compact Main menu Graphics 14.5 Graphics/current values Main menu Graphics/current values Here, one or several channels can be se- lected for the recording and representation of measuring data, for example from a dew point sensor or several different sensors. After having pressed this button, the currently recorded measuring data are displayed in the current time range.
Page 93
Operation METPOINT® BDL compact Main menu Graphics/current values #1- #6 Under this menu item, up to four channels (depending on the version of the ® METPOINT BDL compact) can be acti- vated simultaneously and viewed under Main menu Graphics/current.
Operation METPOINT® BDL compact 14.6 Channels Main menu Channels Halle 1.1 Druckluft Halle 1.2 Druckluft 0.750 m³/h 1165.200 m³/h 7366 m³ 27366 m³ 80.000 m/s 180.000 m/s current values view shows the current measured values of all the connected sensors. Halle 2.1 Taupunkt Halle 2.2 Taupunkt In the event that the adjusted alarm limits are...
Operation METPOINT® BDL compact Main menu Current values Setup Next layout Here, the desired layout can be selected by pressing the Next Layout button. It is possible to choose between six different layouts with the indication of between one and five measured values.
Operation METPOINT® BDL compact This is an alarm-1 for channel A1 and an alarm-2 for channels A2 and B1! Main menu Alarm overview A1 As with Main menu Channels, individual channels can be selected here. In the alarm overview, it is quickly visible which measured value has exceeded or un-...
Page 97
Operation METPOINT® BDL compact Main menu Export data Export logger data Selection The selected date is always highlighted in green, and the date figures of the Sundays are red, as is the case in a calendar. On days on which the measuring data were recorded, the date figures are optically raised.
Operation METPOINT® BDL compact 14.10 Screenshot function By means of this function, a copy of the display in the menus graphics, graphics/current values, channels, and current values can be stored on a USB stick or SD card. 14.10.1 Storing the screenshot Main menu ...
Operation METPOINT® BDL compact 14.10.2 Exporting screenshots The screenshots that are stored on the SD card can be exported to a USB stick. Main menu Export data With Export screenshots,the stored screen- shots can be transmitted to a USB stick. Main menu ...
SD card and battery Main menu Export data Export screenshots Exporting Ausgewählte Dateien: Tot. Size(Kbyte): The screenshots of the selected period of time are exported to a USB stick. 15 SD card and battery For the storage and further processing of the recorded measuring results, there is an SD card slot inside the BDL housing.
Law 7 (ElektroG), the METPOINT BDL from BEKO TECHNOLOGIES GmbH is taken back to be disposed If the BDL compact is not returned to BEKO TECHNOLOGIES GmbH for disposal, it must be disposed of in accordance with waste code: 20 01 36 Used electrical and electronic devices with the exception of those which come under 20 01 21, 20 01 23, and 20 01 35.
Declaration of conformity 18 Declaration of conformity METPOINT® BDL compact...
Page 103
Declaration of conformity BEKO TECHNOLOGIES GMBH 41468 Neuss, GERMANY Phone: +49 2131 988-0 www.beko.de EC Declaration of Conformity We hereby declare that the products indicated hereafter, in the delivered performance, comply with the stipu- lations of the relevant EU directives in force. This declaration only refers to products in the condition in which they have been placed into circulation.
Page 104
Analog current signal 4-20mA 25 Processing 25 Danger compressed air 7, 10 Safety advice 7 Danger supply voltage 17 Safety instructions 7, 17 Skilled personnel 17 Field of application 8 Technical data 14 Incorrect installation 7 METPOINT® BDL compact...