Connection/terminal diagram METPOINT® BDL compact
View of the connecting plugs at the back of the device.
Potential-free alarm change-over contacts, connecting plugs A and B
Line cross-section: 0.14 – 1.5 mm
CAUTION!
NC (1) and COM (2) are closed during the following operating conditions:
- in the event of an alarm
- in the event of a sensor break
- in the event of a voltage breakdown
Load of the potential-free alarm contacts:
min. switching current
max. switching voltage
max. switching current (acc. to VDE)
Contact material
METPOINT® BDL compact
/ AW G 16 - AW G 28
2
10 mA
250V AC / 30V DC
3 A
AgNi (silver nickel)
1 = NC = Normally Closed
2 = COM
3 = NO = Normally Open