11 Connection/terminal diagram METPOINT
View of the connecting plugs at the back of the device.
All of the connections at the back of the device are designed as pluggable screw terminal blocks. For
the connection, the following needs to be observed:
• Line cross-section for the power cable, plug C : 0.75 – 2.5 mm
• Line cross-section for alarm contacts, plug A / B : 0.14 – 1.5 mm
• Line cross-section for sensors : 0.14 – 1.5 mm
DANGER!
Supply voltage!
An incorrect connection during the installation works involves risks for persons and the material,
and a malfunction of the BDL compact may occur.

11.1 Pin assignment plug "C" (supply voltage)

Input voltage range: 85 ... 264 V AC / 47 ... 63 Hz / 1 Ph. / PE
Line cross-section: 0.75 – 2.5 mm
20
Connection/terminal diagram METPOINT® BDL compact
2
/ AWG16 - AWG28
/ AW G 12 - AW G 24
2
1 = PE = protective conductor / earth
2 = L = phase L
3 = N = neutral lead N
®
BDL compact
2
/ AWG12 - AWG24
2
/ AWG16 - AWG28
METPOINT® BDL compact