Technical data
Technical data for blinker transmitter
Mechanical lifetime
Silver plated contacts:
U min.
U max.
I max. AC current
I max. DC current
Technical data for handwheel activation switches
Mechanical lifetime
Silver plated contacts:
U min.
U max.
I max. AC current
I max. DC current
13.2.

Technical data Actuator controls

Features and functions
Power supply
External supply of the electronics
(option)
Current consumption
Overvoltage category
Rated power
Switchgear
Control inputs
74
SA 07.2
SA 16.2 / SAR 07.2
7
10
starts
10 V AC/DC
250 V AC/DC
3 A at 250 V (resistive load)
2 A at 250 V (inductive load, cos phi ≈ 0.8)
0.25 A at 250 V (resistive load)
6
10
starts
12 V DC
250 V AC
3 A at 250 V (inductive load, cos phi = 0.8)
3 A at 12 V (resistive load)
Refer to name plate
Permissible variation of mains voltage: ±10 %
Permissible variation of mains voltage: ±30 % (optional)
Permissible variation of mains frequency: ±5 %
24 V DC +20 %/ 15 %
Current consumption: Basic version approx. 250 mA, with options up to 500 mA
External power supply must have reinforced insulation against mains voltage in accordance with IEC
61010-1 and may only be supplied by a circuit limited to 150 VA in accordance with IEC 61010-1.
Current consumption of the actuator controls depending on mains voltage:
For permissible variation of mains voltage of ±10 %:
100 to 120 V AC = max. 740 mA
208 to 240 V AC = max. 400 mA
380 to 500 V AC = max. 250 mA
515 to 690 V AC = max. 200 mA
For permissible variation of mains voltage of ±30 %:
100 to 120 V AC = max. 1,200 mA
208 to 240 V AC = max. 750 mA
380 to 500 V AC = max. 400 mA
515 to 690 V AC = max. 400 mA
Category III according to IEC 60364-4-443
The actuator controls are designed for the nominal motor power, refer to motor name plate
Standard:
Reversing contactors (mechanically and electrically interlocked) for AUMA power classes
A1/A2
Options:
Reversing contactors (mechanically and electrically interlocked) for AUMA power class
A3
Thyristor unit for mains voltage up to 500 V AC (recommended for modulating actuators)
for AUMA power classes B1, B2 and B3
The reversing contactors are designed for a lifetime of 2 million starts. For applications requiring a high
number of starts, we recommend the use of thyristor units.
For the assignment of AUMA power classes, please refer to Electrical data on actuator
6 digital inputs: OPEN, STOP, CLOSE, EMERGENCY (via opto-isolator, thereof OPEN, STOP, CLOSE
with one common and EMERGENCY without common, respect minimum pulse duration for modulating
actuators).
SAR 16.2 Control unit - electromechanical
AC 01.2 Intrusive