28
Install POINT I/O Modules
Rockwell Automation Publication 1734-UM001E-EN-P - July 2013
Channel
Output
1B
3
2A
4
2B
6
3A
5
3B
7
(1) Supply voltage can range from +5V DC... 240V AC, depending on relay load.
12/24V DC power for the module is provided by the external power supply.
The power supply voltage may be daisychained from a 1734 adapter, 1734-FPD module,
or 1734-EP24DC power supply communication interface. Each channel is individually
isolated and may have a unique supply or voltage as necessary.
ATTENTION: Do not attempt to increase load current or wattage
capability beyond the maximum rating by connecting two or more
outputs in parallel. The slightest variation in relay switching time may
cause one relay to momentarily switch the total load current.
Make certain that all relay wiring is properly connected before applying any
power to the module.
Total current draw through the wiring base unit is limited to 10 A. Separate
power connections to the terminal base unit may be necessary.
Use the end cap from your adapter or interface module to cover the exposed
interconnections on the last mounting base on the DIN rail. Failure to do so
could result in equipment damage or injury from electric shock.
Relay Modules Using AC Only
PDN
OW2
OW2
0 1
0 1
0 1
AC Power Bus
120V AC
Common
(1)
Supply