Allen-Bradley 1734-IM4 User Manual page 149

Point series i/o digital and analog modules; pointblock series i/o modules
Table of Contents

Advertisement

Subnet and POINTBus Status
Off
Device is not online.
• Device has not completed Dup_MAC_ID test.
• Device is not powered - check module status indicator.
Flashing green
Device is online but has no connections in the established state.
Solid green
Device is online and has connections in the established state.
Flashing red
No scanlist is available. I/O module is missing.
Solid red
Critical link failure - failed communication device present. Device detected
error that prevents it from communicating on the network.
Indicator
Indication
System Power
Off
Green
Field Power
Off
Green
Probable Cause
Field power is OFF, or DC-DC converter problem.
System power is on. DC-DC converter is active (5V).
Field power is off.
Power is on with 24V present.
Rockwell Automation Publication 1734-UM001E-EN-P - July 2013
Troubleshoot with the Indicators
Check adapter status indicator to determine if more
time is needed to complete the dup_MAC_id test
or if the adapter needs to be powered.
None.
None.
1. Make sure all I/O modules are connected and
using the correct MAC IDs.
2. Check Cycling Node Status parameter in
RSNetWorx for DeviceNet software.
1. Make sure an I/O module is not using a
MAC ID = 0.
2. Make sure all backplane modules are
communicating at the proper communication
rate.
Recommended Action
1. Verify field power is on.
2. Verify backplane power (load current) is not
exceeded.
3. Replace 1734-ADN(X) adapter.
None.
Turn field power on.
None.
151