Configure POINT I/O Modules for DeviceNet Networks
Rockwell Automation Publication 1734-UM001E-EN-P - July 2013
5. From the Device Parameters dialog, set Run or Idle, noting that any
parameter with a lock indicated next to it is nonchangeable..
6. Select values for current or voltage.
For current, click one of the following:
• 4...20 mA
• 0...20 mA
For voltage, click one of the following:
• 0...10V
• -10...+10V
Note that fault states include the following:
• Hold Last state
• Go to Low Clamp
• Go to High Clamp