Allen-Bradley 1734-IM4 User Manual page 185

Point series i/o digital and analog modules; pointblock series i/o modules
Table of Contents

Advertisement

For This Value
High Engineering
Low Engineering
Digital Filter (ms)
Current Range
Voltage Range
Real Time Sample (ms)
Notch Filter
Real Time Sample Values
Real Time
Notch Filter Setting
Sample
50 Hz
Min
120 ms
You see a Configuration dialog for a current or voltage module, based on
the type of module you added. See the figure for a Configuration dialog
for a current input module.
2. From the Configuration dialog, complete entries, referring to the table.
Select
-32768...32767
-32768...32767
0...10000
4...0 mA
0...20 mA
-10...10V
0...10V
0...10000
50 Hz
60 Hz
250 Hz
500 Hz
60 Hz
100 ms
3. From the bottom of the Configuration dialog, perform one of the
following:
• Click another tab at the top of the dialog.
or
Rockwell Automation Publication 1734-UM001E-EN-P - July 2013
Configure POINT I/O Modules in RSLogix 5000 Software
Comments
Default for 1734-IE2C analog input module is 16383.
Default for 1734-IE2V analog input module is 10000.
Default for 1734-IE2C analog input module is 3277.
Default for 1734-IE2V analog input module is 0.
Default is 0.
Default is 4...20 mA.
Default is 0...10V
Default is 100.
Refer to the Real Time Sample Values table for the relationship between
Notch Filter and Real Time Sample.
Default is 60 Hz.
Refer to the Real Time Sample Values table for the relationship between
Notch Filter and Real Time Sample.
250 Hz
500 Hz
24 ms
12 ms
193