Allen-Bradley 1734-IM4 User Manual page 113

Point series i/o digital and analog modules; pointblock series i/o modules
Table of Contents

Advertisement

ATTENTION: Whatever field power you supply is connected to the
internal field-power bus. For example, if 120V AC is applied to the
power connections, there will be 120V AC applied to the modules
through the internal field-power bus.
POINT I/O modules to the right of the module will also have that
internal power bus voltage applied, unless you use a 1734-FPD,
1734-EP24DC, or 1734-EPAC module to interrupt and change the field
power-bus voltage.
I/O messages are sent to (consumed) and received from (produced) the
POINT I/O modules. These messages are mapped into the processor's memory.
The 1734D-IB8XOB8E module produces one byte of input data (scanner Rx)
status. It consumes one byte of output data (scanner Tx).
Default Data Map for the 1734D-IB8XOB8E DC Input/Output Module
Message Size: 1 Byte
7
Produces
Ch7
(scanner Rx)
Where: 0 = off, 1 = on
Message Size: 1 Byte
7
Consumes
Ch7
(scanner Tx)
Where: 0 = off, 1 = on
The 1734D-IB8XOW8 module produces one byte of input data (scanner Rx)
status. It consumes one byte of output data (scanner Tx).
Default Data Map for the 1734D-IB8XOW8 DC Input/Relay Output Module
Message Size: 1 Byte
7
Produces
Ch7
(scanner Rx)
Where: 0 = off, 1 = on
Message Size: 1 Byte
7
Consumes
Ch7
(scanner Tx)
Where: 0 = off, 1 = on
Rockwell Automation Publication 1734-UM001E-EN-P - July 2013
6
5
4
3
2
Ch6
Ch5
Ch4
Ch3
Ch2
6
5
4
3
2
Ch6
Ch5
Ch4
Ch3
Ch2
6
5
4
3
2
Ch6
Ch5
Ch4
Ch3
Ch2
6
5
4
3
2
Ch6
Ch5
Ch4
Ch3
Ch2
POINT I/O Module Data
1
0
Ch1
Ch0
Input Data
1
0
Ch1
Ch0
Output Data (or
state)
1
0
Ch1
Ch0
Input Data
1
0
Ch1
Ch0
Output Data
115

Hide quick links: