Allen-Bradley 1734-IM4 User Manual page 153

Point series i/o digital and analog modules; pointblock series i/o modules
Table of Contents

Advertisement

Indication
Probable Cause
Flashing red
1 Hz - Check_Configuration telegram rejected.
Max number of POINT I/O modules in master configuration
overridden.
2 Hz - SetPrm telegram rejected.
The first byte in user parameter data does not equal zero. Max
number of user parameter bytes overridden.
Indication
Probable Cause
POINTBus Status
Off
• No power supplied.
• Hardware check is in progress.
• Initialization is in progress.
Solid green
Normal operation present.
Flashing red
1 Hz - Incorrect POINT I/O module installed.
POINT I/O module removed from backplane.
Solid red
Critical link failure (BUS_OFF) is present.
Indicator
Indication
System Power
Off
Green
Field Power
Off
Green
Probable Cause
System power not applied.
System power (5V) present
Field power not applied.
Field power (24V) applied.
Rockwell Automation Publication 1734-UM001E-EN-P - July 2013
Troubleshoot with the Indicators
Recommended Action
Check configuration.
Recommended Action
Apply power.
None.
Verify module installation, no modules removed, and correct,
as needed.
Check network cabling, and correct, as needed.
Recommended Action
1. Verify field power is on.
2. Verify backplane power (load current) is not exceeded.
3. Replace 1734-APB adapter.
None.
Apply field power (24V).
None.
155