Carrier Aero 39MN Series Installation, Start-Up And Service Instructions Manual page 92

39mn,mw03-110 series indoor and weathertight outdoor air handlers
Table of Contents

Advertisement

FACE VIEW
(BLADES SHOWN OPEN)
39M
UNIT
SIZE
A
B
72W
113.00
46.00
85W
132.00
46.00
96W
132.00
52.00
110W
150.00
52.00
LEGEND
AMS
— Air Measuring Station
NOTE: A and B dimensions are actual to O.D. of damper frames not including flanges.
SIDE VIEW
A / 3
E1
B1 D1
B
B2 D2
.219 ± .031 DIA. HOLES at 6" C-C
WITH RANDOM START POINT
DIMENSIONS (in.)
A/3
B1
B2
37.60
27.60
18.40
44.00
27.60
18.40
44.00
31.20
20.80
50.00
31.20
20.80
Fig. 29 — AMS Damper Dimensions (cont)
15.00
X1 ± .25
X2 ±.25
A
A / 3
E1
SIZES 72-110
X1
X2
D1
11.74
11.96
24.60
11.74
11.96
24.60
13.52
14.36
28.20
13.52
14.36
28.20
92
a39-4306
.50 TYP.
4 CORNERS
A / 3
.25 DIA HOLES
E1
TYP. 4 CORNERS
.50 TYP.
4 CORNERS
AIR
MEASUREMENT
DAMPER
.44 TYP.
4 SIDES
(TYP.)
PREMIUM
DAMPER
AMS
LOW
LIMIT
D2
E1
(CFM)
15.02
35.42
6,115
15.02
41.71
7,208
16.85
41.71
8,148
16.85
47.72
9,174
AMS
HIGH
LIMIT
(CFM)
40,768
48,052
54,319
61,159

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents