39M UNIT SIZE
CIRCUITING TYPE
Airflow (cfm) at 500 fpm
Total Face Area (sq ft)
Tubes in Face
Tube Length (in.)
No. of Circuits - Total
4-Row Coil
Face Split Coils
No. of TXVs
Suction Connections (in. OD)
Distributor Connections (in. OD)
Distributor Nozzle Size
Intertwined Row Split Coils
No. of TXVs
Suction Connections (in. OD)
Distributor Connections (in. OD)
Distributor Nozzle Size
Single Circuit Coils
No. of TXVs
Suction Connections (in. OD)
Distributor Connections (in. OD)
Distributor Nozzle Size
6-Row Coil
Face Split Coils
No. of TXVs
Suction Connections (in. OD)
Distributor Connections (in. OD)
Distributor Nozzle Size
Intertwined Row Split Coils
No. of TXVs
Suction Connections (in. OD)
Distributor Connections (in. OD)
Distributor Nozzle Size
Single Circuit Coils
No. of TXVs
Suction Connections (in. OD)
Distributor Connections (in. OD)
Distributor Nozzle Size
8-Row Coil
Face Split Coils
No. of TXVs
Suction Connections (in. OD)
Distributor Connections (in. OD)
Distributor Nozzle Size
Intertwined Row Split Coils
No. of TXVs
Suction Connections (in. OD)
Distributor Connections (in. OD)
Distributor Nozzle Size
Single Circuit Coils
No. of TXVs
Suction Connections (in. OD)
Distributor Connections (in. OD)
Distributor Nozzle Size
LEGEND
TXV — Thermostatic Expansion Valve (Field Supplied)
*When 2 nozzle sizes are listed, the smaller nozzle should be located on the upper distrib-
utor.
Table 12 — Direct-Expansion Circuiting Data (cont)
Large Face Area Coils (cont)
96W
Full
48,125
96.3
44
44
44
126
126
126
44
44
88
Upper
Lower
Upper
4
4
1-3/8
1-3/8
1-1/8
1-1/8
E-12
E-12
4
4
1-3/8
1-3/8
1-1/8
1-1/8
E-12
E-12
4
4
1-3/8
1-3/8
1-1/8
1-1/8
E-12
E-12
4
4
1-3/8
1-3/8
1-1/8
1-1/8
E-12
E-12
4
4
8
1-3/8
1-3/8
1-3/8
1-1/8
1-1/8
1-1/8
E-12
E-12
E-12
4
4
8
1-3/8
1-3/8
1-3/8
1-1/8
1-1/8
1-1/8
E-12
E-12
E-12
Double
44
44
126
144
88
44
Lower
Upper
4
1-3/8
1-1/8
E-12
4
1-3/8
1-1/8
E-12
4
1-3/8
1-1/8
E-12
4
1-3/8
1-1/8
E-12
8
4
1-3/8
1-3/8
1-1/8
1-1/8
E-12
E-12
8
4
1-3/8
1-3/8
1-1/8
1-1/8
E-12
E-12
NOTE: Factory-supplied distributors have factory-selected nozzle sizes as shown. If necessary,
replace factory-supplied nozzles with field-supplied and field-installed nozzles. Consult
AHUBuilder
®
software selection program for correct nozzle selection.
54
110W
Full
Double
55,000
110.0
44
44
144
144
44
88
Lower
Upper
4
1-3/8
1-1/8
E-12
4
1-3/8
1-1/8
E-12
4
1-3/8
1-1/8
E-12
4
1-3/8
1-1/8
E-12
4
8
1-3/8
1-3/8
1-1/8
1-1/8
E-12
E-12
4
8
1-3/8
1-3/8
1-1/8
1-1/8
E-12
E-12
44
144
88
Lower
8
1-3/8
1-1/8
E-12
8
1-3/8
1-1/8
E-12