NOTES:
1. All conductors are no. 22 AWG (American Wire Gage) minimum.
2. Install jumpers if fire/smoke detector, low limit thermostat, or high pressure switch are not required.
Fig. 110 — Field-Supplied Control Wiring for VFD Speed Control
From a Field Supplied 4 Wire
Static Pressure Transducer
*Acceptable transducer output voltage ranges are 0-10 vdc, 0-5 vdc, and 2-10 vdc. Default sensor range is 0-10 vdc from factory. Use parame-
ters 4008 to configure sensor low voltage and parameter 4009 to configure sensor high voltage.
NOTES:
1. All conductors are no. 22 AWG (American Wire Gage) minimum.
2. Install jumpers if fire/smoke detector, low limit thermostat, or high pressure switch are not required.
3. Program static pressure control set point using parameter 4011 in volts vdc.
Fig. 111 — Field Wiring for Stand-Alone Static Pressure Control with 4-Wire Static Pressure Transducer
* 0-10 v dc
+
Output Signal
-
Field Supplied
Input Connections
Jumper
N.O. Start / Stop Contact
N.C. Fire / Smoke Det. Contact
N.C. Low Limit Thermostat
N.C. High Pressure Switch
(Voltage Output)
1
1 1
AI-2 Cable Shield Ground
2 2
2
3
3 3
4 4
4
5
5 5
AI-2 Static Pressure Signal (+) 0 - 10 v dc
6
6 6
AI-2 Static Pressure Signal (-) 0 - 10 v dc
7 7
7
8 8
8
9
9 9
24 Vdc
10 10
10
11 11
11
Ground – DC Common
12 12
12
Digital Input Common
DI-1 Start / Stop
13 13
13
14
14 14
DI-2 Run Enable
15 15
15
16 16
DI-4 Start Enable 1
DI-5 Start Enable 2
17 17
18
DI-6 Internal PID Enable
142