Distributor Nozzle Change-Out; Filter Drier - Carrier Aero 39MN Series Installation, Start-Up And Service Instructions Manual

39mn,mw03-110 series indoor and weathertight outdoor air handlers
Table of Contents

Advertisement

COIL
CASING
TXV
UPPER
SENSING
SPLIT
BULB
AIRFLOW
15 DIAMS
MIN
10
DIAMS
LOWER
SPLIT
TXV
SENSING
BULB
AIRFLOW
15
DIAMS
MIN
10
DIAMS
a39-2366
LEGEND
TXV — Thermostatic Expansion Valve
Fig. 95 — Face Split Coil Suction-Line Piping
TXV SENSING
BULBS
AIRFLOW
10 DIAMS
15
DIAMS
MIN
15
DIAMS
MIN
10 DIAMS
EVAPORATOR COIL
FIRST-ON, LAST-OFF
LEGEND
TXV — Thermostatic Expansion Valve
Fig. 96 — Row Split Coil Suction-Line Piping
UNIT
CASING
SOLENOID
SIGHT
VALVE
GLASS
FILTER
DRIER
8
DIAMS
SOLENOID
MIN
VALVE
SIGHT
GLASS
FILTER
DRIER
TXV
INSIDE
CASING
(TYP)
DISTRIBUTOR
(TYP)
8 DIAMS
MIN
EVAPORATOR
COIL
FIRST-ON, LAST-OFF
COIL
UNIT
CASING
CASING
SOLENOID
VALVE
SIGHT
GLASS
FILTER
DRIER
SOLENOID
VALVE
SIGHT
GLASS
FILTER
DRIER
8
DIAMS
MIN
TXV
8
INSIDE
DIAMS
CASING
MIN
(TYP)
DISTRIBUTOR
(TYP)
a39-2367
Distributor Nozzle Change-Out —
zles are factory supplied. Thermostatic expansion valves (TX-
Vs) are either field or factory supplied. Be sure that correct
nozzle is installed in each distributor before installing expan-
sion valve. See Table 11 for factory-installed distributor nozzle
sizes. Use AHUBuilder
performance; replacement nozzles must be field-installed. The
correct nozzle is typically factory-installed.
Do not overheat distributor or cap. Failure to comply could
result in equipment damage.
Perform nozzle change-out procedure as follows:
1. Remove plastic end cap by using an electric heat gun
or a torch (see Fig. 97).
2. Clean off any grime.
3. Remove nozzle retaining ring with screwdriver or nee-
dle nosed pliers.
4. Remove nozzle from distributor by inserting 2 no. 6-
32 threaded rods (at least 4 in. long) into the threaded
holes provided in the nozzle. See Fig. 98.
5. Insert correct nozzle into distributor body.
6. Re-insert nozzle retainer ring into distributor.
PLASTIC CAP
WITH VALVE
a39-4174
Fig. 97 — Distributor and Cap
NOZZLE
RETAINER
RING
SIMPLIFIED NOZZLE
REMOVAL
G
5
NO. 6-32 THREADED
PULLER HOLES
Fig. 98 — Nozzle Change-Out
A filter drier should be installed before the
Filter Drier —
TXV to ensure satisfactory valve operation.
127
Distributor noz-
®
program to select nozzles for best
CAUTION
BODY
TUBING
THREADED
a39-2041
PULLER RODS

Hide quick links:

Advertisement

Table of Contents
loading