Carrier Aero 39MN Series Installation, Start-Up And Service Instructions Manual page 87

39mn,mw03-110 series indoor and weathertight outdoor air handlers
Table of Contents

Advertisement

Fig. 24 — Attaching Split Sections — Non-Stacked Units and Lower Level of Stacked Units
10. If CCH (coil connection housing) is installed at a section
split:
a. Use the Intelliclamp connectors on the vertical
frames and the split brackets on the top frames to
bring the sections together.
b. Remove the upstream side panels to gain access to
the inner surface of the frames.
c. Use tool clearance holes to install ¼-in. screws into
the downstream frame for the permanent section
joint (only necessary on the CCH side). Detail D in
Fig. 25 shows the location of the holes; the number
of holes will vary by unit.
d. Reinstall upstream access panel.
e. Remove the Intelliclamp connectors, the split sec-
tion L bracket, and the lifting lug under the section
that match the CCH side walls and install the CCH
as described in Coil Connection Housing section
on page 110.
11. Where fan is blow-thru airfoil or forward-curved, install
fan discharge diffuser to bulkhead.
WARNING
Do not attempt to lift unit after assembly! Severe per-
sonal injury or death can result.
CAUTION
Ensure a good seal is created between both sections before
continuing. Equipment damage could result.
SEE DETAIL A
SEE
DETAIL B
5/16 in.-18 x 2 1/2
SEE DETAIL C
A39-4385
87
SPLIT SECTION L BRACKET
SCREW
SPLIT SECTION
INTELLICLAMP
CONNECTOR
NUT
(5/16 in.-18)
DETAIL B
SCREW
SCREW
NUT (1/2 in.-13)
DETAIL D
Fig. 25 — Attaching CCH at Section Split —
Location of Screw Holes
12. For outdoor units, assemble all roof brackets provided
and caulk roof corners as shown in Fig. 26, Detail B. Also
caulk (using black or grey polyurethane adhesive sealant
such as Black Sikaflex 221 or Silaprene Solid Seal) over
the field section joint seals from top to bottom on the out-
side of each field joint to ensure seal integrity.
NUT (3/8 in.-16)
WASHER (3/8 in.)
SCREW
(3/8 in.-16 x 8 in.)
DETAIL A
DETAIL C
SCREW (1/2 in.-13 x 8 in.)
WASHER (1/2 in.)
a39-4309
SCREW
1/4 in. -
3/4 in.
SEE
DETAIL D
SCALE 7:10

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents