Carrier Aero 39MN Series Installation, Start-Up And Service Instructions Manual page 122

39mn,mw03-110 series indoor and weathertight outdoor air handlers
Table of Contents

Advertisement

condensate outlet holes along the downstream edge. (It
may be helpful to temporarily secure the drain pan by a
strip of double-stick tape on the center hat channel.)
11. Lift the upper coil (with spacer hat channels on the
bottom of each end) into place, aligning the upper coil
with the lower coil. When the upper coil is lowered
BAFFLE, LEFT
CHANNEL, HAT
PAN, CONDENSATE
CENTERED WITHIN SECTION
a39-2988ef
Fig. 85 — Single Slope Condensate Drain — Apply Gasket
BAFFLE, TOP
BAFFLE, CENTER
Fig. 86 — Double Slope Condensate Drain — Apply Gasket
into place, it will deflect the intermediate condensate
pan downward on each end, providing for positive
drainage.
12. Install factory-supplied screws around the ends and top
of the coil.
CHANNEL, HAT
COIL FRAMES
BAFFLE, RIGHT
ANGLE
ATTACHED TO COILS
BOTH SIDES
IMPORTANT: ADHESIVE GASKET MUST BE
APPLIED TO THE FULL LENGTH OF THE BOTTOM
BAFFLE MATING FLANGE TO CREATE SEAL BETWEEN
THE COIL SIDE CASING AND THE BAFFLE.
SEE ILLUSTRATION BELOW.
BAFFLE, BOTTOM
APPLY FLUSH TO THIS EDGE
GASKET, ADHESIVE
122
BOTTOM BAFFLE

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents