Carrier Aero 39MN Series Installation, Start-Up And Service Instructions Manual page 141

39mn,mw03-110 series indoor and weathertight outdoor air handlers
Table of Contents

Advertisement

GROUP
PARAMETER
NUMBER
NUMBER
3101
3102
3103
3104
31
3105
3106
3107
3108
3415
3416
3417
34
3418
3419
3420
3421
4001
4002
4005
4006
4007
40
4010
4011
4012
4013
4016
4027
5301
5303
5304
53
5305
5310
5311
98
9802
* Factory Programmed as follows: For 208-230v / 60 Hz = 208, 460v / 60 Hz = 460, 200-230v / 50 Hz = 200, 380 / 50 Hz = 400.
† Motor Nameplate Amps. Factory programmed per Programmed Settings in Table 37. This value should always be compared to the actual motor nameplate value
before start-up.
**Maximum Output Amps — Factory programmed per Table 37.
Table 38 — Air Handler VFD Factory-Set Parameters (cont)
DESCRIPTION
Number of Retries
Trial Time
Delay Time
AR Overcurrent
AR Overvoltage
AR Under voltage
AR AI< Minimum
AR External Fault
Signal Parameter 3
Signal 3 Minimum
Signal 3 Maximum
Output 3 DSP From
Output 3 DSP units
Output 3 Minimum
Output 3 Maximum
Gain
Integration Time
Error Value Invert
Units
Display Format
Setpoint Select
Internal Setpoint
Setpoint Minimum
Setpoint Maximum
ACT 1 Input
PID Parameter Set
EFB Protocol ID
EFB Baud Rate
EFB Parity
EFB Control Profile
EFB PAR 10
EFM PAR 11
Comm Prot SEL
VFD DRIVE ONLY
PARAMETERS
2
600 sec.
5 sec.
Enable
Enable
Enable
(0) Disable
(0) Disable
Speed
0
30000
0
rpm
0
3000
0.7
30 sec.
no
volts
x.xxx
Internal
Field Program (0.0v~10,0v)
0 v
10.0v
AI-2
SET 1
0
9.6
8 NONE 1
ABB DRV LIM
0
0
NOT SEL
141
VFD WITH E-CLIPSE DESCRIPTION /
PARAMETER
2
600 sec.
5 sec.
Enable
Enable
Enable
(0) Disable
(0) Disable
Speed
0
30000
0
rpm
0
3000
0.7
30 sec.
no
volts
x.xxx
Internal
Field Program (0.0v~10,0v)
0 v
10.0v
AI-2
SET 1
118
76.8
8 EVEN 1
DCU PROFILE
103
104
STD MODBUS