3 Technical Specifications
3.1 Power Supply Specifications
The power supplies in Table 10 may be used for PS1 only, or for both PS1 and
PS2 on the RSG2300, but only for PS1 on the RSG2300P. The RSG2300P uses
the PoE power supply specified in Table 11 for PS2.
Power Supply
Type
12 – 24 VDC
48 VDC
HI (125/250 VDC)
HI (110/230 VAC)
Table 10: Power Supply Specifications
Power Supply
Type (PS2)
48 VDC
Table 11: PoE Power Supply Specifications
Notes:
1. The "HI" power supply is the same power supply for both AC and DC.
2. (F) Denotes fast-acting fuse, (T) denotes time-delay fuse
3. Power consumption varies based on configuration. 10/100Base-TX ports
consume roughly 1W less than fiber optic ports
3.2 Failsafe Relay Specifications
Parameter
Max Switching Voltage
Rated Switching Current
Max Switching Capacity
RuggedCom®
Input Range
Min
Max
10 VDC
36 VDC
36 VDC
59 VDC
1
88 VDC
300 VDC
1
85 VAC
264 VAC
Input Range
Min
Max
37 VDC
72 VDC
240VAC, 125VDC
2A @ 240VAC
0.15A @ 125VDC, 2A @ 30VDC
150W, 500VA
31
RuggedSwitch RSG2300 Installation Guide Rev108
Technical Specifications
Internal
Max. Power
Fuse
Consumption
Rating
2
6.3A(F)
2
3.15A(T)
1,2
2A(T)
Internal
Max. Power
Fuse
Consumption
Rating
2
2A(T)
Value (Resistive Load)
3
25W
68 W