2.3.2 DC Power Supply Wiring Examples (RSG2300 and
RSG2300P)

Figure 21: DC Power Supply Wiring Examples

Notes:
RSG2300P will always have a 48VDC power supply in position PS2.
125/250VDC rated equipment: A 300VDC appropriately rated circuit breaker
must be installed.
A circuit breaker is not required for 12-24 or 48 VDC rated power supplies.
For dual DC power supplies, separate circuit breakers must be installed and
separately identified.
Equipment must be installed according to the applicable country wiring
codes.