C O N F I G U R I N G T H E M OTO R M A N A G E M E N T F U N C T I O N S
The following parameters are set according to the requirements (Req 1, Req2, Req 5):
Settings for local mode 1 (For busfault situation)
Loc 1 Start Bus Cyc
Loc 1 Stop Bus Cyc
Loc 1 Start DI
Loc 1 Stop DI
Loc 1 Start LCD
Loc 1 Stop LCD
Loc 1 Start Bus Acyc
Loc 1 Stop Bus Acyc
Settings for Auto/Remote mode (S1 in position Remote)
Auto Start Bus Cyc
Auto Stop Bus Cyc
Auto Start DI
Auto Stop DI
Auto Start LCD
Auto Stop LCD
Auto Start Bus Acyc
Auto Stop Bus Acyc
Settings for local mode 2 (Switch S1 in position Local)
Loc 2 Start Bus Cyc
Loc 2 Stop Bus Cyc
Loc 2 Start DI
Loc 2 Stop DI
Loc 2 Start LCD
Loc 2 Stop LCD
Loc 2 Start Bus Acyc
Loc 2 Stop Bus Acyc
The following diagram shows the simplified UMC internal data flow if S1 is in position Remote as shown in the circuit diagram
before.
On the left side there are the four blocks representing the control stations. Only three of them were required in the example.
In the middle the so-called command control selection block is displayed. On the right the starter function block is displayed.
The configuration is as above. A cross represents a YES, an empty field a NO.
The active mode is REMOTE/AUTO as defined by S1.
Therefore the DCS can start the motor.
Other start commands (as indicated by DI4) will be blocked.
UMC
Control
Stations
...
DI4
Digital
DI5
Inputs
DI0
0
LCD
Panel
Cyclic Bus
Telegram
1
Acyclic
Bus
Telegram
Bus
0
Super-
vision
Force Local 2
Automode
Fieldbus
Busfault
= YES (Req. 1)
= NO
= YES (Req 5)
= YES (Req 5)
= YES (Req 5)
= YES (Req 5)
= NO
= NO
= YES (Req 2)
= YES (Req 2)
= NO
= YES (Req 2)
= NO
= YES
= YES
= YES
= NO
= YES (Req. 1)
= YES (Req. 1)
= YES (Req. 1)
= YES (Req. 1)
= YES (Req. 1)
= NO
= NO
Mode
enable
Selection
Starter
Function
(e.g. DOL)
Start
Stop
63