U M C 1 0 0 . 3 U N I V E R S A L M O T O R C O N T R O L L E R T E C H N I C A L D E S C R I P T I O N
150
General
Tightening torque for the input, output and supply terminals
Net weight
Degree of protection
Temperature range
Marks, Approvals
Relay Outputs
Number of relay outputs
Voltage range of contacts
Uimp
Short-circuit protection
Lowest switched power for correct signals
Switching of inductive power
Switching capacity per relay contact acc. to EN 60947-5-1
(electromagnetic load)
Relay contact service life
Internal clearance and creepage distances of relay
contacts to 24 V circuits
ø 4,5 mm / 0.177 in / PH 1
0.22 kg
IP20
storage -25 ... +70 °C
operation 0 ... +55 °C (DX122-FBP.0) / +60 °C (DX111-FBP.0)
CE, cUL, CCC, EAC
4
1DO1, 1DO2 with root 1DOC
2DO3, 2DO4 with root 2DOC
12-250 V AC/DC
4 kV
6 A gG per root (1DOC, 2DOC)
1 W or 1 VA
Inductive loads need additional measures for spark suppression. Diodes for DC
voltage and varistors / RC elements for AC voltage are suitable. Some DC coil
contactors contain rectifiers which suppress sparks perfectly.
AC-15 240 V AC: max. 1,5 A
AC-15 120 V AC: max. 3 A
DC-13 250 V DC max. 0.11 A
DC-13 125 V DC max. 0.22 A
DC-13 24 V DC max. 1 A
Mechanical 500 000 switching cycles
Electrical (250 V AC):
0.5 A: 100 000 cycles
1.5 A 50 000 cycles
> 5.5 mm (safety insulation up to 250 V AC)
(EN 60947-1, Pollution degree 2)
Pollution degree terminals: 3
0.6 ... 0.8 Nm
5.31 ... 7.08 in.lb
7mm
2 x 0.5 ... 4 mm
0.28 in
2 x 20 ... 12 AWG
7mm
2 x 0.75 ... 2.5 mm
0.28 in
2 x 18 ... 14 AWG
7mm
2 x 0.75 ... 2.5 mm
0.28 in
2 x 18 ... 14 AWG
2
2
2