Indicator
Locked Rotor
Thermal model reached
warning level
PTC overtemperature
PTC wiring problem
Check-back error
Motor current below low
current trip threshold
Motor current below low
current warning threshold
Motor current above high
current trip threshold
Motor current above high
current warning threshold
Earth fault (external or internal
sensor) above trip threshold
Earthfault current above
warning threshold
Selftest UMC HW
Actuator problem
IO module missing
Custom application error (e.g.
download incomplete)
IO module error
Aux1: Error or warning
triggered from auxiliary
function block input 0
Aux2: Error or warning
triggered from auxiliary
function block input 1
Aux3: Error or warning
triggered from auxiliary
function block input 2
Aux4: Error or warning
triggered from auxiliary
function block input 3
Aux5: Error or warning
triggered from auxiliary
function block input 4
Aux6: Error or warning
triggered from auxiliary
function block input 5
Multifunction input 0
Multifunction input 1
Multifunction input 2
Code
Source / Root Cause
3
Load Side
4
Load Side
5
Load side
Environment
6
Summary message. See detailed
messages for more information.
7
Summary message. See detailed
messages for more information.
8
Process
Load side
Load side mechanics
9
Process
Load side
Load side mechanics
10
Load side
11
Load side
12
Load side electrical
13
Load side electrical
14
Electronics
15
Load side mechanics
16
Electronics, Wiring
17
Configuration
18
Electronics
19
User-defined
20
User-defined
21
User-defined
22
User-defined
23
User-defined
24
User-defined
25
User-defined
26
User-defined
27
User-defined
Possible Cause / Suggested Action
The rotor is locked. Load too heavy for motor.
Thermal model reached warning level. If overload condition remains
a trip soon follows.
Check motor load condition
Check for mechanical problems
PTC element indicated that motor temperature is too high
Check motor environment and load conditions
See codes 83/84
See codes 80...82
Motor current is below user-defined threshold e.g. motor running
idle, dry running pump, conveyer belt broken ...
Check motor load and motor / process conditions. Wait until
cooling time is over.
Motor current is below user-defined threshold e.g. motor running
idle, dry running pump, conveyer belt broken ...
Check motor load and motor / process conditions
Motor current above threshold caused e.g. by jammed equipment
Check process conditions (remove blocking cause). Wait until
cooling time is over.
Motor current above user-defined threshold.
Check motor load and motor / process conditions.
Connection between one or more phases and ground
Check wiring / motor (isolation problem)
See above
Hardware fault detected, more details see under no. 128...140;
On LCD panel: -> maintenance/service -> Diagnosis -> Error history
Replace UMC
Open/close time of actuator exceeded because of tight valve or
other mechanical reasons.
Check runtime parameter and limit and torque switch wiring
Communication cable not connected. Cable break or IO module
hardware error.
An unrecoverable error was detected while processing the custom
application (e.g. checksum error)
The version of application editor and UMC are not compatible
A self-test error was detected in an IO module.
Check the LEDs on the module
Replace the module
The digital input of an IO module has created a trip/warning.
Reason depends on what you have connected to the input.
Note: If the "AuxWarnFault" function block is used in a different way
than in the predefined applications also other inputs than the
DX1xx can be the fault source.
A multifunction input of the UMC has triggered a trip.
The reason depends on what you have connected to the input.