U M C 1 0 0 . 3 U N I V E R S A L M O T O R C O N T R O L L E R T E C H N I C A L D E S C R I P T I O N
116
Indicator
PTC wire break
PTC short-circuit
DX111/DX122 module missing
AI111 AM1 module
missing
AI111 AM2 module
missing
VX1xx module missing
Overload analog output DX111/
DX122
Wire break analogue output
DX111/DX122
Single phase mode not
supported
U below trip/warn level
U above trip/warn level
AM1 CH1/2/3 Wire break
AM2 CH1/2/3 Wire break
Sensor error
AM1 CH1/2/3
Sensor error
AM2 CH1/2/3
AM1 CH1/2/3 Out of range
AM2 CH1/2/3 Out of range
P below trip/warn level
PF below trip/warn level
Phase loss (voltage)
Phase imbalance
(voltage)
Voltage out of range
Wrong Phase Sequence
(voltage)
Code
Source / Root Cause
83
Wiring
84
Wiring
85
Wiring, Electronics
86
Wiring, Electronics
87
88
92
Wiring, connected meter has a
defect
93
Wiring
94
Configuration
95, 96
Motor supply voltage is too low.
97, 98
Motor supply voltage is too high.
99,102,105
Wiring / 4-20mA input
108,111,114
100,103,106
Wiring / temperature sensor
109,112,115
101,104,107
Load side
110,113,127
Configuration
116, 117
Active power consumption of the
motor is too low.
120, 121
Active power consumption of the
motor is too low
122
No voltage on one or more phases.
Possible causes are a blown fuse
or a wire break.
123
There is a high imbalance on
supply side e.g. because of
unsymmetrical load of the three
phases.
124
The voltage is out of the specified
voltage range
125
The phases were wired in incorrect
order.
Possible Cause / Suggested Action
Check between UMC and motor
Check wiring between UMC and motor
The IO module does not respond during start-up of UMC.
Check wiring between UMC and module
Check supply of module
Check status LEDs of the module
Check wiring, short circuit at analogue output
Check Wiring
A voltage module not supporting single phase mode was
configured for single phase mode. Use a voltage module with
production index A5 or later.
Check supply side: E.g. circuit breaker, fuses, wiring and the
feeding.
Check supply side: E.g. circuit breaker, fuses, wiring and the
feeding.
Check wire between AM1 and signal source
Check wire between AM1 and temerature sensor
Check that the configured sensor type is correct
Check that the correct sensor type is connected
Check that the delivered sensor signal in range.
Either the motor is idle (not loaded) or the motor load is not
connected because of a broken belt or a dry running pump etc.
Check load side
Either the motor is idle (not loaded) or the motor load is not
connected because of a broken belt or a dry running pump etc.
Check load side
Check fuses
Check wiring on supply side.
Check supply side especially the fuses and supply line.
Check supply side. See 95 – 98.
Check wiring