PA R A M E T E R S A N D D ATA S T R U C T U R E S O N A F I E L D B U S
Protection Parameters Continued
Parameter
Parameter
Number
Name
Voltage Dip / Load Shedding
142
Dip Enable
143
Voltage Dip
Duration
144
Autorestart
Window
145
Autorestart
Delay
147
Enable
Autorestart
156
Dip Restart
Level
157
Dip Level
Internal Ground Fault
10
Earth Flt Trip
Level
11
Earth Flt Trip
Delay
12
Earth Flt Warn
Level
13
Earth Flt Warn
Delay
16
Earth Flt
Detection
Description, Explanations
Enable / Disable function
Max. voltage dip duration time before a trip is signalled.
If the voltage dip ends within this time window an autorestart is
triggered (if enabled).
Delay until the motor is restarted
Enables the autorestart of the motor after end of the voltage dip
Voltage level indicating the end of the low voltage situation
Voltage level indicating a low voltage situation and triggering the
DIP logic.
Above this ground fault current a ground fault tip is triggered.
A value of 255 % disables the trip.
Delay time until a ground fault trip is triggered.
Trip happens after the configured delay time plus a internal
calculation time of about 600ms.
Above this ground fault current a ground fault warning is
triggered.
A value of 255% disables the warning.
Delay time until a ground fault warning is triggered.
Warning happens after the configured delay time plus a internal
calculation time of about 600ms.
Mode of internal ground fault protection: Defines when the
internal ground fault protection is active.
Options
Off (0),
On (1),
On + Rapid Cycle Lockout (2)
0.1...25.5s in steps of 0.1s
Default: 0.5s
Unscaled: 1...255
Example: 5 means 0.5s
0.1 ... 1s in steps of 0.1s
Unscaled: 1...10
Example: 5 means 0.5s
0 ... 255s
Off (0)
On (1)
50 ... 115% of U
in steps of 1%
e
Default value: 90
50 ... 115% of U
in steps of 1%
e
Default value: 70
20 ... 80 in % of nominal current
I
(255 = off)
e1,2
Default value is 255
Example: Ie = 100A, Earth Flt
Trip Level = 35%. Then a earth
fault current of 35A triggers a
trip.
0...25.5s in steps of 0.1s
Default: 0,5s
Unscaled: 0...255
Example: 20 means 2s
20 ... 80 in % of nominal current
I
(255 = off)
e1,2
Default value is 255
0...25.5s in steps of 0.1s
Default: 0,5s
Unscaled: 0...255
Example: 20 means 2s
Always (0)
After Startup (1)
129
Adjustable via
UMC100-PAN
PBDTM
All excluding
GSD-PDQ22
UMC100-PAN
PBDTM
UMC100-PAN
PBDTM
UMC100-PAN
PBDTM
All
All
All excluding GSD
PDQ22
All excluding GSD
PDQ22
All