PA R A M E T E R S A N D D ATA S T R U C T U R E S O N A F I E L D B U S
Motor Management Parameters Continued
Parameter
Parameter
Number
Invert control (ctrl) Inputs
82
Inv DI start input
83
Inv DI stop input
Multifunction Inputs: The following parameters are all related to DI0-DI2 which are called multifunction inputs as their function can be
adjusted in a wide range.
(1.13)
117, 118, 119
Multif. 0,1,2 delay
120, 121,
Multif. 0,1,2 auto reset
122
135/136
Multif. 0,1,2 fault text
137/138
Line 1, Line 2
139/140
114,
Multifunction 0,1,2
115,
116
Extended
23
Checkback time
15
Emergency Start
14
Fault auto reset
81
Custom app parameter
177
Param To PV 1
178
Param To PV 2
179
Param To PV 3
180
Param To PV 4
181
Param To PV 5
Description, Explanations
If inverted (Yes) the DI is normally closed. If not
inverted (No) it is normally open.
If inverted (Yes) the DI is normally closed. If not
inverted (No) it is normally open.
Delay until the function of DI0,1,2 is triggered
If DI0,1,2 is configured as external fault an auto
reset can be enabled.
If DI0,1,2 is configured as an external fault a text
message can be defined which is shown on the
LCD panel.
Function of DI0/1/2.
NC: Normally closed
NO: Normally open
1)
Motor running or stopped
Always when the motor is running
2)
The maximum delay between the output relay
was closed until the checkback signal is present
(signal at DI0 present or motor current > 20 %
depending on parameter Checkback)
To allow start-ups even if the thermal overload
protection would prevent them.
Automatically reset of selected protection faults
(PTC, overload (EOL), imbalance and phase loss).
Faults triggered from the UMC100 multifunction
inputs and the IO module are not automatically
reset. There are separate parameters.
Allows to specify a value which is available in the
custom application.
Selection of Processvalue 1 that is transferred via
fieldbus
Selection of Processvalue 2 that is transferred via
fieldbus
Selection of Processvalue 3 that is transferred via
fieldbus
Selection of Processvalue 4 that is transferred via
fieldbus
Selection of Processvalue 5 that is transferred via
fieldbus
Options
No (0), Yes (1)
No (0), Yes (1)
0...25,5 in steps of 0,1s
Unscaled: 0...255
Example: A value of 5 means 500ms
No (0),
Yes (1)
Line one and line two with 8
characters each.
Default: „Fault DIx" where x=0,1,2
Off (0):
Stop NC (1),
Stop NO (2),
Ext. Flt NC always
(3),
1
Ext. Flt NO always
1
(4),
Ext. Flt NC Motor on (5),
Ext. Flt NO Motor on (6),
Prep. emergency start NC (7),
Prep. emergency start NO (8)
Test position NC (9),
Test position NO (10),
Force local NC (11)
Force local NO (12)
Fault reset NC (13),
Fault reset NO (14),
Voltage DIP NC (15),
Voltage DIP NO(16),
CEM11 always
(Warn) (17),
2
CEM11 after startup (Warn) (18),
CEM11 always
(Fault) (19),
2
CEM11 after startup (Fault) (20)
0.1, 0.2, 0.3, 0.4 ,0.5 ... 25.5 in steps
of 0.1s
Unscaled: 0...255
Example: A value of 5 means 500ms
Off (0), On (1)
Off (0), On (1)
0 ... 255
1
2
3
4
5
125
Adjustable
via
All
All
PBDTM, LCD
Panel
UMC100-PAN
All
All excluding
GSD-PDQ22
All
All
All
UMC100-PAN
PBDTM
UMC100-PAN
PBDTM
UMC100-PAN
PBDTM
UMC100-PAN
PBDTM
UMC100-PAN
PBDTM