U M C 1 0 0 . 3 U N I V E R S A L M O T O R C O N T R O L L E R T E C H N I C A L D E S C R I P T I O N
154
Analog Inputs
Number of inputs
Type of analog inputs (adjustable)
Resolution
Meausuring ranges
0...20 mA and 0...10 V
4...20 mA
Max. input current for 0/4-20mA
Accuracy at 20°C (T20)
Temperature coefficient
Input resistance
Wire break detection
Cable shielding
EMC UMC100.3, AI111.0, DX1xx-FBP.0 and VI15x-FBP.0
Measurement of radiated and conducted interference according to
EN61131-2 CISPR16-2-3
Electrostatic discharge accoring to IEC 61000-6-2
Radiofrequency electromagnetic field according to IEC 61000-4-3
Fast transient bursts according to EN61000-4-4
High energy surges according to EN61000-4-5
Conducted radio frequency interference according to EN61000-4-6
VI15x-FBP.0
High energy surges according to EN61000-4-5
Damped oscillatory wave acc. to
EN61000-4-18
Immunity low frequency harmonics acc. to EN61000-4-11
3 (one AI111.0) / 6 (two AI111.0)
0/4 mA - 20 mA / 0-10 V
15 Bit
0 .... 27648 dec (6C00 hex)
0 .... 27648 dec (6C00 hex)
60 mA (destruction limit)
±1 % from full scale value
0.05 / K deviation from T20
m 300 Ohm at 0/4 -20mA
M10kOhm at 0-10V
In operation mode: 4 mA - 20 mA
Recommended for up to 30 m and outside the switchgear cabinet; shielding
mandatory for cables over 30 m
Class A
Notice:
This product has been designed for environment A.
Use of this product in environment B may cause
unwanted electromagnetic disturbances in which
case the user may be required to take adequate
mitigation measures.
8 kV air discharge
6 kV contact discharge
10 V/m
2 kV power supply
1SAJ530000R1***: 2/1 kv CM/DM
Others: 1/0.5 kV CM/DM
10 V
1/0.5 kV CM/DM power supply
2/1 kV CM/DM L1/L2/L3 voltage inputs
Only voltage inputs L1/L2/L3:
2.5 kV / 1 kV CM / DM
Power supply: 50 ... 12 kHz, 3 V