ABB UMC100.3 Manual page 130

Univeral motor controller
Hide thumbs Also See for UMC100.3:
Table of Contents

Advertisement

U M C 1 0 0 . 3 U N I V E R S A L M O T O R C O N T R O L L E R T E C H N I C A L D E S C R I P T I O N
130
Communication Parameters
Parameter
Parameter
Number
Name
17
Address check
18
Busfault
reaction
-
Bus
address
-
Parameter lock
-
I/O Data profile
-
DeviceNet
baudrate
-
MODBUS
baudrate
-
MODBUS Frame
-
MODBUS bus
timeout
-
IP setting mode
-
IP address, octet
1..4
-
Subnet mask,
octet 1..4
-
Gateway, octet
1..4
-
Enable
Webserver
-
Retrofit
Description, Explanations
Enable check if bus address stored in the UMC is the same as the
one stored in the communication interface.
UMC behaviour in the event of a bus fault.
Fieldbus address. Depending on the communication
interface used, the permitted address range is smaller
than the one allowed here.
Prevents any parameter changes if set to On.
Set length of I/O data
Baudrate used if connected via DNP31 into a DeviceNet network
Baud rate used if connected via MRP31 to a Modbus RTU network
Frame type used if UMC is connected via MRP31 to a
Modbus RTU network (number of data bits, parity, number
of stop bits)
Note: older versions of UMC100/UMC100.3 do not send
this parameter, then an autodetection function is active
The master has to send a telegram within the given time
otherwise the UMC triggers the configured busfault reaction.
Mode how the IP address settings are made
Note: in Basic Mode the IP address is created automatically as
192.168.0.xxx where (xxx = set by "Bus Address"
Parameter)
IP address used if connected via Ethernet communication module to
Ethernet network
Subnet mask used if connected via Ethernet communication module
to Ethernet network
Gateway-IP address used if connected via Ethernet communication
module to Ethernet network
Enable/Disable webserver when connected to an Ethernet network
To set UMC100.3 to UMC100-FBP.0 mode for backward compatibilty
Options
Off (0), On (1)
Motor Off (0),
Retain (1),
Start For (2),
Start Rev (3)
0,1,2,3 ...255
Unlocked (0), Locked (1)
Profile 1, Profile 2
Autobaud (0)
125 kBaud (1)
250 kBaud (2)
500 kBaud (3)
1200 Baud (0)
2400 Baud (1)
4800 Baud (2)
9600 Baud (3)
19200 Baud (4)
57600 Baud (5)
8 Data, even, 1 Stop (1)
8 Data, odd, 1 Stop (2)
8 Data, no, 2 Stop (3)
8 Data, no, 1 Stop (4)
0 (off) ... 255s
DHCP (0)
Basic (1)
User defined (2)
0..255
Default: 192.168.0.1
0..255
Default: 255.255.255.0
0..255
Default: 0.0.0.0
Off (0)
On(1)
Off (0)
UMC100-FBP (1)
Adjustable via
All
All
UMC100-PAN
PBDTM
UMC100-PAN
UMC100-PAN
UMC100-PAN
UMC100-PAN
UMC100-PAN
UMC100-PAN
UMC100-PAN
UMC100-PAN
UMC100-PAN
UMC100-PAN
UMC100-PAN
UMC100-PAN

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents