U M C 1 0 0 . 3 U N I V E R S A L M O T O R C O N T R O L L E R T E C H N I C A L D E S C R I P T I O N
148
Thermistor Motor Protection (PTC - binary) Type A
Isolation
Fieldbus Connection
Mounting
Suitable communication interfaces
Environmental and mechanical data
Mounting
Mounting position
Dimensions (W x H x D)
Net weight
Wire size and tightening torque
Tightening torque for screw mounting
Degree of protection
Temperature range storage
Temperature range operation
Marks, approvals
Operation altitude above sea level
Performance Data
Reaction time UMC100 DI to UMC100 Relay Output
(incl. hardware delays).
Reaction time UMC100 DI to DX111-FBP.0 Relay Output
(incl. hardware delays)
Reaction time from DX111-FBP.0 DI to UMC100 Relay Ouput
(incl. hardware delays)
Number of supported function blocks:
No
On UMC or remote with single mounting kit SMK3.0
Fieldbus:
PROFIBUS: PDP32.0 or PDQ22
Modbus: MRP31.0
DeviceNet: DNR31
Ethernet:
ModbusTCP
PROFINET IO
Older Fieldbus Plugs are compatible, but can not be plugged on the UMC100.3.
1SAJ530000R0***
On DIN rail (EN 50022-35) or with 4 screws M4
Any
70 x 105 x 106 mm
0.3 kg
ø 3,5 mm / 0.138 in
0.8 Nm
UMC: IP20
-25 ... +70 °C
0 ... +60 °C with two output relays
activated
CE, cUL, CCC, EAC
ATEX for 1SAJ530000R0200, 1SAJ530000R1200
Up to 5000 m
Operation above 4000m only with isolated motor wires
typ. 10 ms (Transparent Control Function)
typ. 10 ms (Transparent Control Function)
typ. 14 ms (Transparent Control Function)
See 2CDC135014D02xx
1SAJ530000R1***
0.35 kg
0.5 Nm
4.5 in.lb
1x 0.2 ... 2.5 mm²
7mm
1x 28 ... 12 AWG
7mm
1x 0.2-2.5 mm²
1x 28 ... 12 AWG
0.28 in
0 ... +60 °C with two relay outputs
activated and 24 V DC supply output
loaded with 250 mA
0 ... +50 °C with two relay outputs
activated and 24 V DC supply output
loaded with 450 mA