T E C H N I C A L D ATA
AI111.0
General
Mounting
Mounting position
Dimensions (W x H x D)
LEDs: Red/yellow/green
Supply voltage
Supply current
Tightening torque for the communication terminals
Tightening torque for the input, output and supply terminals
Net weight
Degree of protection
Temperature range
Marks, Approvals
Functional isolation between anlog inputs and 24 V DC supply /
communication interface
Indiviual configuration of each analog input
U
sensor analog inputs
imp
Pollution degree terminals
Operation altitude above sea level
Temperature Inputs
Type of connection
Number of input channels
Type of temperature inputs (adjustable per channel)
Accuracy at 20 °C (T20)
Temperature coefficient
Out of range detection
Max. cable length
Cable shielding
Update rate
Sensor current (typ.)
On DIN rail (EN 50022-35)
Any
See Dimensions of expansion modules
Red: Hardware error of module
Yellow: Diagnosis available
Green: Ready for operation
24 V DC (+30 % ... -20 %)
(19.2 ... 31.2 V DC) including ripple
Max. 40 mA (at 19.2 ... 31.2 V DC)
see section DX1xx
see section DX1xx
0.118 kg (0.260 lb)
IP20
storage -25 ... +70 °C
operation 0 ... +60 °C
CE, cUL
Further in preparation. Ask your local sales representative for other marks/
approvals.
yes
yes
0.5 kV
3
Up to 5000 m
2 or 3 wire
3 (one AI111.0) / 6 (two AI111.0)
PT100 -50 °C...+400 °C
PT100 -50 °C...+70 °C
PT1000 -50 °C...+400°C
KTY83-110 -50 °C...+175 °C
KTY84-130 -40 °C...+300 °C
NTC +80...+160 °C [B75227-K333-A1]
m± 2 K
0.1K per K deviation from T20
yes
max. cable resistance: 50R (single wire)
[e.g. with copper wire 1.5mm²: 1900m cable length]
Recommended for up to 30 m and outside the switchgear cabinet; shielding
mandatory for cables over 30 m
typ. 600 ms
PT100 1 mA
PT1000/KTY83/KTY84/NTC 0.2 mA
153