U M C 1 0 0 . 3 U N I V E R S A L M O T O R C O N T R O L L E R T E C H N I C A L D E S C R I P T I O N
126
Motor Management Parameters Continued
Parameter
Parameter
Number
Limit the Number of Starts
148
Num Starts Allowed
149
Num Starts Window
150
Num Starts Pause
155
Num Starts Overrun
221
Num Starts Prewarn
Maintenance related parameters
192
Motor operating hours level
193
Motor stand still level
Description, Explanations
Defines the number of permissible starts in the
time window.
Defines a time window in which only a certain
number of starts are allowed.
After the motor was stopped a new start is not
possible before the pause time is over.. This
paramter can be used independantly of the other
parameters i.e. without limiting the number of
starts in a time window.
Reaction if no start is left anymore but a start
command was issued.
Reaction if only one start is left.
After the defined number of weeks of motor
operation a warning is triggered.
After the defined number of weeks of continous
motor stand-still time a warning is triggered.
Options
0 ... 32
Zero switchs off the start limit
function.
0min ... 255min (4,25h) in steps of
1min
Default value: 0
0min ... 255min (4,25h) in steps of
1min
Default value: 0
0: Disabled
1: Trip
2: Warning
0: Disabled
1: Trip
2: Warning
0 ... 255 (weeks)
Default value is 0 that disables the
supervision
Adjustable
via
All excluding
GSD-PDQ22
All excluding
GSD-PDQ22
All excluding
GSD-PDQ22
All excluding
GSD-PDQ22
All excluding
GSD-PDQ22
All