U M C 1 0 0 . 3 U N I V E R S A L M O T O R C O N T R O L L E R T E C H N I C A L D E S C R I P T I O N
146
Power consumption (typ.)
UMC100.3
Transistor output DO3
PDP32.0
MRP31.0
DNP31.0
EIU32.0
UMC100-PAN
DX111-FBP.0
DX122-FBP.0-FBP.0
VI150-FBP.0
VI155-FBP.0
AI111.0
UMC100.3 UC 1SAJ530000R1*** provides 24 V DC supply for expansion modules, transistor output DO3
and communication interface.
Max current is:
450 mA / T
=50 °C
u
250 mA / T
=60 °C
u
Following examples for the calculation of the load on '24 V out'
UMC100.3 UC
6 DI high, 2 Relays on
PTC=1.5 kΩ; output DO3 off
current in mA
PDP32.0
41
DX111-FBP.0
125
VI155-FBP.0
33
AI111.0
35
UMC100-PAN
14
Transistor output DO3=off
0
Sum
248
PDP32.0
41
DX111-FBP.0
125
VI155-FBP.0
33
AI111.0
35
UMC100-PAN
14
Transistor output
50
DO3=50 mA
Sum
298
Digital Inputs
Number of digital inputs
Supply for digital inputs
Conditions
6 DI high; 3 Relays on
PTC=1.5 kΩ; In (motor)=4A
Depends on load
max current 250 mA
12Mbit; SUB-D with termination
57.6 kbit
ETH1 and ETH2 active
Backlight on
all DI high, all DO high
all DI high, all DO high
U
= 400 V AC
n
U
= 400 V AC
n
1SAJ530000R0***
P [W]
I [mA]
3
120
0...6
0...250
1
41
0.6
27
0.5
20
2.2
90
0.3
14
3
125
2
82
0.6
27
0.8
33
0.8
35
Max load on '24 V Out'
Tu=50 °C
450 mA
=> ok up to Tu=60 °C
=> ok up to Tu=50 °C
6 (DI0 ... DI5)
Type 1 accord. to EN 61131-2
24 V DC
1SAJ530000R1***
P [W]
S [VA]
3.5
8
0...1.5
0...2.5
1.2
2
0.8
1.2
1.0
1.5
3.2
5.8
0.5
1
3.5
5.5
2.5
4.5
0.8
1.2
1.0
1.5
1.0
1.5
Tu=60 °C
250 mA