U M C 1 0 0 . 3 U N I V E R S A L M O T O R C O N T R O L L E R T E C H N I C A L D E S C R I P T I O N
128
Protection Parameters Continued
Parameter
Parameter
Number
Name
Phases
42
Phase loss
protection
43
Curr Imb Trip
Level
44
Curr Imb Warn
Level
45
Phase
reversal
46
Check phase
sequence
Over - and Undercurrent
32
Low curr trip
level
34
Low curr warn
level
33
Low curr trip
delay
35
Low curr warn
delay
36
High curr trip
level
38
High curr warn
level
37
High curr trip
delay
39
High curr warn
delay
Description, Explanations
Trips the motor depending of the trip class within 1.5 -12 seconds
in case of a phase loss. This parameter must be set to On during
regular operation.
Phase imbalance (current) trip threshold. Above this value a trip is
generated. This function is activated together with the phase
loss protection.
Phase imbalance (current) warning threshold. Above this value a
warning is generated. This function is activated together with the
phase loss protection.
If enabled the three phases must be fed through the UMC CTs in
the correct order (L1 left, L2 middle, L3 right).
Enables supervision of phase sequence (L1/L2/L3)
Value in % of I/I
. Below this value a trip is generated. A value of
e
0% disables the trip.
Value in % of I/I
. Below this value a warning is generated. A value
e
of 0% disables the warning.
Delay time until a low current trip is triggered.
Delay time until a low current warning is triggered.
Value in % of I/I
. Above this value a trip is generated. A value of
e
800% (160) disables the trip.
Value in % of I/I
. Above this value a warning is generated. A value
e
of 800% (160) disables the warning
Delay time until a high current trip is triggered..
Delay time until a high current warning is triggered.
Options
Off (0), On (1)
Note: If the voltage module
is present this parameter
activates both voltage and
current based phase loss
detection.
0...100%
Default value: 50
0...100%
L1L2L3 (0),
L3L2L1 (1)
Note: If the voltage module
is present this parameter must
not be changed.
Disabled (0),
Trip (1),
Warning (2)
Note: If the voltage module
is present this parameter
activates both voltage and
current based phase sequence
protection.
0...100% in steps of 5%
Default: 0%
0% disables the function
Unscaled: 0 ... 20
Example: 10 means 50%
0...100% in steps of 5%
Default: 50%
0% disables the function
Unscaled: 0...20
Example: 10 means 50%
0...25.5s in steps of 0.1s
Default: 0.5s
Unscaled: 0...255
Example: 20 means 2s
0...25.5s in steps of 0.1s
Default: 0.5s
Unscaled: 0...255
Example: 20 means 2s
100...800 in steps of 5%
Default: 800%
800% disables the function
Unscaled: 20...160
Example: 100 means 500%
(100% is nominal current)
100...800% in steps of 5%.
Default value is 150%.
800% disables the function
Unscaled: 20...160
Example: 100 means 500%
(100% is nominal current)
0...25.5s in steps of 0.1s
Default: 0.5s
Unscaled: 0...255
Example: 20 means 2s
0...25.5s in steps of 0.1s
Default: 0.5s
Unscaled: 0...255
Example: 20 means 2s
Adjustable via
All
All excluding
GSD-PDQ22
All excluding
GSD-PDQ22
All excluding
GSD-PDQ22
All excluding
GSD-PDQ22
All
All
All excluding
GSD-PDQ22
All excluding
GSD-PDQ22
All
All
All excluding
GSD-PDQ22
All excluding
GSD-PDQ22