E R R O R H A N D L I N G , M A I N T E N A N C E A N D S E R V I C E
Indicator
OK Stamp
Abgl. Checksum
FRAM read/write
Param D invers
Thermal capacity
VCC voltage
12VP voltage
12VN voltage
PTC channel
Flash Checksum
curr. meas. channel
Selftest UMC_HW1
Voltage DIP
Parameter up/download
AM1 CH1/2/3 HH/H
AM2 CH1/2/3 HH/H
AM1 CH1/2/3 LL/L
AM2 CH1/2/3 LL/L
AM1 max. temperature
AM2 max. temperature
Motor stand still hours
exceeded
Error parameter inverters
invers
Code
Source / Root Cause
128
OK Stamp not correct or missing
129
Calibration checksum
130
FRAM error
131
Parameter storage error
132
Thermal capacitor error
133
VCC voltage
134
12VP voltage
135
12VN voltage
136
PTC_Channel
137
Flash Checksum in microprocessor
139
current measure channel
140
Summery fault
(RAM, CPU, ....)
144
Undervoltage / no voltage
situation is too long
145
A problem occured during
parameter exchange between the
UMC and the LCD panel.
146,148,150
Value on senser > configured
152,154,156
HH/H level
147,149,151
Value on senser < configured L/LL
153,155,157
level
158
In temperature mode:
159
Temperature of one of the sensors
connected to
AM1 is above configured maximal
temperature
160
Motor did not run for a long time
161
Invalid parameter from auto save
Possible Cause / Suggested Action
Hardware fault detected during selftest
Replace UMC
The DIP took longer than configured in parameter Voltage Dip
Duration
Check that the parameters / application stored in the LCD panel
can be handled from the used UMC.
Do not remove the panel while parameter exchange
Do not remove power while parameter exchange.
Check process
Check process
Check motor/process conditions
Start motor to check everyting is still fine
Load correct parameters
117