U M C 1 0 0 . 3 U N I V E R S A L M O T O R C O N T R O L L E R T E C H N I C A L D E S C R I P T I O N
152
VI150-FBP.0 and VI155-FBP.0
General
Mounting
Mounting position
Dimensions (W x H x D)
LEDs: Red/yellow/green
Supply voltage
Supply current (relay activated)
Tightening torque for the input, output and supply terminals
Tightening torque for the communication terminals
Net weight
Degree of protection
Temperature range
Marks, Approvals
Operation altitude above sea level
Relay Outputs
Number of relay outputs
Voltage range of contacts
U
imp
Other technical data for the relay outputs see the DX1xx module
Voltage Inputs L1, L2, L3
Overvoltage category
Nominal input range
U
imp
Voltage measuring in the nominal input range
Power factor: 0.4 ... 0.95
Real power kW
Energy kWh
THD %
Rated Operational Voltage U
e
Usage in grounded/ungrounded networks
Voltage supply cables
On DIN rail (EN 50022-35)
Any
A distance of 10 mm left and right to the L1 and L3 terminals might be
necessary depending on the other devices mounted beside for voltages
> 230 V / 400 V respectively
22.5 x 77 x 100 mm
(excluding communication connector)
Red: Error of module
Yellow: Diagnosis available
Green: Ready for operation
24 V DC (+30 % ... -20 %)
(19.2 ... 31.2 V DC) including ripple
VI150-FBP.0: Max. 40 mA (at 19.2 ... 31.2 V DC)
VI155-FBP.0: Max. 55 mA (at 19.2 ... 31.2 V DC)
See DX1xx module
See DX1xx module
0.11 kg
IP20
storage -25 ... +70 °C
operation 0 ... +60 °C
CE, cUL, CCC, EAC
VI150-FBP.0: max. 2000 m
VI155-FBP.0: max. 4000 m at 60 °C
For higher altitudes please contact your sales unit.
1
DO0 with root DOC
12-250 V AC/DC
4 kV
III in grounded networks
II in ungrounded networks
90 - 690 V AC (three-phase mode)
90 - 400 V AC (single-phase mode)
8 kV
+/- 2 %
+/- 5 % typ. for I > 0.75 A
+/- 5 % typ.
+/- 5 % typ.
5% typ.
690 V AC line to line (three phase mode)
400 V AC line to earth (single phase mode)
VI155-FBP.0 can be used in grounded and ungrounded networks
VI150-FBP.0 can only be used in grounded networks. See installation
instructions in section 2
Note that the connection cables for voltage measurement may require
additional cable protection